FC Series w/ EDC Control
Thermal
MNL-047-A
Division Rev.
004
FTS
17
Stone Ridge, NY USA
845.687.0071
LOW TEMPERATURE
Check the setting of the low temperature alarm (LA) by pressing and holding the 1/0
button to enter the program mode, then using the
Δ
and
∇
keys find the SPAn menu,
press 1/0 until LA is displayed, note the temperature for LA.
Press 1/0 until the controller returns to operation mode and then touch
Δ
or
∇
to
show the current setpoint.
Then either increase the temperature setpoint to ensure it is set above the low
temperature alarm setting (LA), or adjust the LA value so that it is lower than the
desired setpoint. Contact the FTS Service Division if the condition persists.
How Reported:
Description:
How Detected:
Appropriate
Response:
The display will flash LA, an audible alarm is sounded, and the system will cease
all refrigeration. The pump and compressor will disengage if the condition persists
for more than 30 seconds.
Indicates that the temperature of the process is lower than the level set for the the
low temperature alarm (LA). The user can set the temperature that this alarm will be
triggered by altering the value for LA in the SPAN menu.
A user positioned thermocouple monitors temperature.