FC Series w/ EDC Control
Thermal
MNL-047-A
Division Rev.
004
FTS
14
Stone Ridge, NY USA
845.687.0071
MISCELLANEOUS MENU
LA
Low Alarm
HA
High Alarm
SH
Span High
SL
Span Low
An alarm can be set to alert the user that the process temperature is too high. Should the HA be
triggered, the system will go to FULL COOL and the display will flash HA. The temperature
alarms are monitored even if the system is in IDLE, in case the user turns off the system without
removing the load; in such an instance, however, the unit is incapable of supplying full cool, and
it is the responsibility of the user to correct the anomaly.
Same as HA, except the system will stop all refrigeration and display LA
Both HA and LA require user reset; clear the messages by pressing the
∇
key. They will not
disappear even if the process returns to the correct level.
SH defines the maximum allowable setpoint. Adjust the values of Span High
and Span Low to define the range of setpoints acceptable for your particular
application.
SL defines the minimum setpoint in this range.