IMPORTANT!
When configuring "PV Point" backup power mode, the information in chapter
on
page
When configuring "Full Backup" backup power mode, the information in chapter
on page
must be observed.
Backup power nominal voltage
When backup power mode is activated, the nominal voltage of the public grid must be
selected.
State of charge warning limit
A warning is output when the residual capacity of the battery specified here is reached in
backup power mode.
Reserve capacity
The set value results in a residual capacity (depending on the capacity of the battery)
that is reserved for backup power. The battery is not discharged below the residual capa-
city in grid-connected operation.
Load management
Up to four pins can be selected for load management here. Additional load management
settings are available in the "Load management" menu item.
Default: Pin 1
Australia - Demand Response Mode (DRM)
The pins for control via DRM can be set here:
Mode
Description
Information
DRM pin
I/O pin
DRM0
Inverter disconnects
itself from the grid
DRM0 occurs if there is an
interruption or short circuit
on the REF GEN or COM
LOAD leads, or if the com-
binations DRM1 - DRM8
are invalid.
The mains relays open.
REF GEN
COM
LOAD
IO4
IO5
DRM1
Import P
nom
≤ 0%
without disconnection
from the grid
currently not supported
DRM 1/5
IN6
DRM2
Import P
nom
≤ 50%
currently not supported
DRM 2/6
IN7
DRM3
Import P
nom
≤ 75% &
+Q
rel
* ≥ 0%
currently not supported
DRM 3/7
IN8
DRM4
Import P
nom
≤ 100%
currently not supported
DRM 4/8
IN9
DRM5
Export P
nom
≤ 0%
without disconnection
from the grid
currently not supported
DRM 1/5
IN6
DRM6
Export P
nom
≤ 50%
currently not supported
DRM 2/6
IN7
DRM7
Export P
nom
≤ 75% &
-Q
rel
* ≥ 0%
currently not supported
DRM 3/7
IN8
DRM8
Export P
nom
≤ 100%
currently not supported
DRM 4/8
IN9
The percentages always refer to the nominal device output.
IMPORTANT!
If the Demand Response Mode (DRM) function is enabled and no DRM control is con-
nected, the inverter switches to Standby mode.
95
EN
Summary of Contents for Primo GEN24 3.0 Plus
Page 2: ......
Page 11: ...General information 11...
Page 12: ...12...
Page 31: ...Backup power variant PV Point OP 31...
Page 32: ...32...
Page 34: ...34...
Page 35: ...Backup power variant Full Backup 35...
Page 36: ...36...
Page 43: ...Installation 43...
Page 44: ...44...
Page 50: ...Do not install the inverter on the ceiling 50...
Page 84: ...84...
Page 90: ...90...
Page 91: ...Settings website of the inverter 91...
Page 92: ...92...
Page 110: ...I O power man agement settings 4 relays 110...
Page 112: ...I O power man agement settings 3 relays 112...
Page 114: ...I O power man agement settings 2 relays 114...
Page 118: ...118...
Page 119: ...Options 119...
Page 120: ...120...
Page 129: ...Appendix 129...
Page 130: ...130...
Page 143: ...Circuit diagrams 143...
Page 144: ...144...
Page 145: ...Circuit Diagram PV Point OP Circuit Diagram 145 EN...
Page 146: ...Fronius Primo GEN24 and BYD Battery Box Premium HV Circuit Diagram 146...
Page 147: ...Automatic switch to backup power 1 pin double separation e g Austria Circuit Diagram 147 EN...
Page 148: ...Automatic switch to backup power 1 pin single separation e g Australia Circuit Diagram 148...
Page 149: ...Automatic switch to backup power 2 pin double separation e g Germany Circuit Diagram 149 EN...
Page 150: ...Automatic switch to backup power 2 pin single separation e g France Spain Circuit Diagram 150...
Page 151: ...Automatic switch to backup power 2 pin double separation e g UK Circuit Diagram 151 EN...
Page 153: ...Fronius Primo GEN24 with Enwitec Box Circuit Diagram 153 EN...
Page 154: ...Wiring diagram surge protective device SPD Circuit Diagram 154...
Page 155: ...Dimensions of the inverter 155...
Page 156: ...156...
Page 157: ...Fronius Primo GEN24 3 6 kW Fronius Primo GEN24 3 6 kW 157 EN...
Page 158: ...158...
Page 159: ...159 EN...