Fronius Primo GEN24 3.0 Plus Operating Instructions Manual Download Page 141

Fronius Primo GEN24

 

4.6 / 4.6 Plus

5.0 / 5.0 Plus

6.0 / 6.0 Plus

Nominal output power (per phase) 

7)

3680 W

Nominal output current (per phase)

16 A

Nominal grid voltage

3 ~ NPE 220 V / 380 V

3 ~ NPE 230 V / 400 V

Nominal frequency for Full Backup

 

53 / 63 Hz 

1)

Switchover time

 

< 90 s

Power factor cos phi 

2)

0 - 1

General data

 

 

 

 

Maximum efficiency

 

97.6%

97.6%

97.6%

European efficiency (U

mpp nom

)

 

97.2%

97.2%

97.1%

European efficiency (U

mpp max

)

 

96.6%

96.7%

96.7%

European efficiency (U

mpp min

)

 

96.2%

96.3%

96.1%

Self-consumption at night

6.8 W

Cooling

 

Controlled forced-air ventilation

Degree of protection

 

IP 66

Dimensions H x W x D

 

528 × 474 × 163 mm

Weight

 

15.4 kg

Permissible ambient temperature

 

-40 °C – +60 °C

Permissible humidity

 

0–100% (incl. condensation)

EMC device class

 

B

DC / AC overvoltage category

 

 

2 / 3

 

Pollution degree

 

2

Sound pressure

 

42 dB(A) (ref. 20µPa)

Safety class (according to IEC62103)

 

1

Protection devices

 

 

 

 

DC insulation measurement

 

Warning / shutdown at R

ISO

 < 600 kOHM

Manifestation of DC overload

 

Operating point shift, power limiter

DC disconnector

 

Integrated

RCMU

 

Integrated

Data communication

 

 

 

 

WLAN SMA-RP connection
(

FCC ID:

 QKWPILOT01 / 

IC ID:

 12270A-PILOT01)

802.11b/g/n (WPA, WPA2)

Ethernet (LAN)

 

RJ45, 10/100 MBit

USB (type A socket)

 

max. 1 A at 5 V (IO connection not connected)

Wired shutdown (WSD)

max. 28 devices/WSD chain

max. distance between two devices = 100 m

Modbus RTU SunSpec (2x)

 

RS485 2-wire

141

EN

Summary of Contents for Primo GEN24 3.0 Plus

Page 1: ...CF sourced from certified sustainable forests FSC Perfect Charging Perfect Welding Solar Energy Fronius Primo GEN24 3 0 Plus 3 6 Plus 4 0 Plus 4 6 Plus 5 0 Plus 6 0 Plus EN Operating instructions Grid...

Page 2: ......

Page 3: ...g mode Inverter with battery further inverter and backup power function 19 Energy flow direction of the inverter 19 Operating states only for systems with a battery 20 Energy saving mode 21 General 21...

Page 4: ...mounting bracket to a wall 51 Installing the mounting bracket on a mast or beam 52 Attaching the mounting bracket to mounting rails 52 Attaching the inverter to the mounting bracket 53 Prerequisites f...

Page 5: ...ral 99 Update 99 Setup wizard 99 Restoring the factory settings 99 Event Log 99 Information 99 Licence manager 100 Communication 102 Network 102 Modbus 103 Safety and grid requirements 105 Feed in lim...

Page 6: ...ircuit Diagram 147 Automatic switch to backup power 1 pin single separation e g Australia 148 Circuit Diagram 148 Automatic switch to backup power 2 pin double separation e g Germany 149 Circuit Diagr...

Page 7: ...the individual poles on the terminals when locking and unlocking General The device has been manufactured in line with the state of the art and according to recognised safety standards In the event o...

Page 8: ...imensioned cables and leads must be immediately repaired by authorised personnel Maintenance and repair work must only be carried out by an authorised specialist It is impossible to guarantee that bou...

Page 9: ...er are mainly electric motors such as Water pumps Circular saws Blowers and fans High starting current Electrical loads that need to accelerate a large mass usually require a high starting cur rent Th...

Page 10: ...arth to protect against elec tric shock in the event of a fault When installing a safety class 1 inverter see Technical data the ground conductor connection is required When connecting the ground cond...

Page 11: ...General information 11...

Page 12: ...12...

Page 13: ...nstallation and commissioning the inverter s operation is fully automatic the inverter draws the maximum possible power from the solar modules Depending on the operating point this power is used in th...

Page 14: ...3 When configuring the photovoltaic system make sure that all components of the photo voltaic system are operating exclusively within their permissible operating range Observe all measures recommended...

Page 15: ...n a loss of power in the inverter Do not block the fan for example with objects that protrude through the touch guard Do not cover the ventilation slots even partially Make sure that the ambient air c...

Page 16: ...e and provides measurement data for energy profiling in Fronius Solar web The primary meter also controls the dynamic feed in control Secondary meter Records the load curve of individual loads e g was...

Page 17: ...ery In order to be able to obtain the highest rate of self consumption with your PV system a battery can be used to store excess energy The battery is coupled to the inverter on the direct current sid...

Page 18: ...d hybrid PV system the inverter can Supply loads in the house Store excess energy in the battery and or feed it into the grid Supply connected loads in the event of a power failure Operating mode Inve...

Page 19: ...rating mode Inverter with bat tery further inverter and backup power function Energy flow dir ection of the inverter In the case of hybrid inverters there are four different energy flow directions 19...

Page 20: ...chieved Battery has reached the minimum SOC set or specified by the manufacturer The battery cannot be discharged any further Energy saving mode standby The system has been put into energy saving mode...

Page 21: ...wing the battery Switch on condi tions If one of the following conditions is met for at least 30 seconds energy saving mode is ended Energy saving mode is no longer permissible owing to a changed sett...

Page 22: ...ons and LED status indicator on page 87 The website of the inverter can be reached All the available data is saved and transmitted to Solar web The real time data can be seen on Solar web Energy savin...

Page 23: ...ing read this document and the Installation Instruc tions for the external battery All the documents relating to the inverter can be found at the following address https www fronius com en solar energ...

Page 24: ...low ing switch on sequence for the system must always be observed 1 Set the DC disconnector to the Off switch position Turn off the automatic circuit breaker 2 Switch on the battery 3 Switch on the au...

Page 25: ...er master fails the operation of the entire WSD chain is interrupted For installation see Installing the WSD wired shutdown on page 85 RCMU The inverter is equipped with a universal current sensitive...

Page 26: ...wn terminal 3 Push in terminals in the data communication area Modbus digital inputs and outputs 4 3 pin push in terminal for PV point OP 5 3 pin AC push in terminal 6 Cable gland strain relief device...

Page 27: ...an be removed for the connection work and must be re inserted 1 Integrated cable duct 2 Recesses for removing the con nection area divider 3 Snap tabs for locking unlocking 4 Defined breaking point fo...

Page 28: ...ter communication IP 169 254 0 180 IOs GND GND V V IO1 IO0 IO3 IO2 IO5 IO4 IN7 IN6 IN9 IN8 IN11 IN10 Load Management Demand Respone Mode DRM Back up power IO control IO4 RG0 Ref GEN 0 IO5 CL0 COM LOAD...

Page 29: ...LAN 2 Ethernet connection only for data com munication from inverter to inverter cur rently unavailable WSD terminal Push in terminal for the WSD installa tion See chapter WSD wired shut down on page...

Page 30: ...severe damage to the inverter Check the polarity of the external power supply with a suitable measuring device before connecting it Connect the cables to the V GND outputs with the correct polarity IM...

Page 31: ...Backup power variant PV Point OP 31...

Page 32: ...32...

Page 33: ...function properly as starting currents are too high for example fridges and freezers It is recommended to switch off non essential loads during backup power mode Overload capacity of 35 is possible f...

Page 34: ...34...

Page 35: ...Backup power variant Full Backup 35...

Page 36: ...36...

Page 37: ...o the country standard and then switches off 4 The inverter starts backup power mode after a checking period 5 All loads in the household that are in the backup power circuit are supplied by the batte...

Page 38: ...prevents unintentional activation of contactors K1 and K2 and thus a grid connection when voltage is restored in the grid The NC auxiliary contacts of contactors K1 and K2 send feedback to the inverte...

Page 39: ...n K4 and K5 drop out This dis connects the backup power circuits and the inverter from the rest of the home net work and from the public grid as the main contacts of the contactors K1 and K2 open at a...

Page 40: ...tability of the returned public grid is determined by checking the measured val ues of the Fronius Smart Meter 5 The inverter ends backup power mode and disconnects the outputs 6 The inverter deactiva...

Page 41: ...id and system protection unit opens contactors K1 and K2 for grid monitoring This disconnects the backup power circuits and the inverter from the rest of the home network and from the public grid as t...

Page 42: ...lic grid is determined by checking the measured val ues of the Fronius Smart Meter 5 On the basis of adjustments that have been carried out the inverter ends backup power mode and disconnects the outp...

Page 43: ...Installation 43...

Page 44: ...44...

Page 45: ...overtorque Use a screwdriver TX20 Do not turn the screws more than 180 Warning notices on the device Technical data warning notices and safety symbols are affixed to the inverter These warning notice...

Page 46: ...ects on the environment and your health RCM symbol the product complies with Australian legislative requirements Safety symbols Risk of serious injury and property damage due to incorrect operation Do...

Page 47: ...een the inverter and the ventilation and building openings on all sides The following surfaces are permissible for installation Walls corrugated metal walls mounting rails brick walls concrete walls o...

Page 48: ...increased risk of accidents from farm animals horses cattle sheep pigs etc Stables or adjoining areas Storage areas for hay straw chaff animal feed fertilizers etc The inverter is essentially designed...

Page 49: ...oping surface with its connection sockets at the top Do not install the inverter at an angle on a vertical wall or column Do not install the inverter horizontally on a vertical wall or pillar Do not i...

Page 50: ...Do not install the inverter on the ceiling 50...

Page 51: ...or screws with a thread diameter of 6 8 mm 0 24 0 32 inches The distance from the left to the right pre drilled hole is 16 inches Unevenness on the mounting surface such as coarse textured plaster is...

Page 52: ...84 000 mounting kit from Rittal GmbH The Pole clamp kit covers the following dimensions Rectangular mast or beam with a side length of 50 150 mm 1 97 5 91 inches Round mast or beam with a diameter of...

Page 53: ...litate lifting attach ing 1 Clip the inverter into the mounting bracket from above The connections must point downwards The lower area of the inverter is pushed into the snap in tabs until the inverte...

Page 54: ...10 mm2 AWG 14 8 2 5 10 mm2 AWG 14 8 2 5 10 mm2 AWG 14 8 2 5 6 mm2 AWG 14 10 PV BAT connections with push in terminal Select a sufficiently large cable cross section based on the actual device output P...

Page 55: ...s with collar Fine stran ded with fer rules without collar Cable recom mendation 300 m 328 yd 10 mm 0 39 inch 0 14 1 5 mm2 AWG 26 16 0 14 1 5 mm2 AWG 26 16 0 14 1 mm2 AWG 26 18 0 14 1 5 mm2 AWG 26 16...

Page 56: ...l current circuit breaker in the AC connection lead For this situation a type A residual current circuit breaker is generally adequate Nev ertheless false alarms can be triggered for the type A residu...

Page 57: ...Inverter Phases AC output Maximum fuse rating Recommen ded fuse rat ing Fronius Primo GEN24 5 0 kW 1 5000 W C 63 A C 40 A Fronius Primo GEN24 6 0 kW 1 6000 W C 63 A C 40 A 57 EN...

Page 58: ...amination Remove contamination in the de energized state Have defective terminals repaired by an authorised specialist IMPORTANT National standards and guidelines regarding load unbalance must be take...

Page 59: ...rain relief device fails the ground conductor is disconnected last For more information on the strain relief device see chapter Cross section of the AC cable on page 55 4 Strip the insulation of the s...

Page 60: ...5 L1 Phase conductor N Neutral conductor PE Ground conductor 6 Insert the AC terminal into the AC slot until it engages Fasten the union nut of the strain relief device with a torque of 6 7 Nm 60...

Page 61: ...that the voltage for the solar modules specified by the manufacturer corresponds to the actual measured voltage IMPORTANT The solar modules connected to the inverter must comply with the IEC 61730 Cl...

Page 62: ...connected to a different number of modules When using for the first time set up the PV generator according to the respective config uration also possible later in the System configuration menu under...

Page 63: ...dule strings to the inverter 1 2 Push the DC cables through the DC bush ings by hand IMPORTANT Before stripping the insulation push the cables through the DC bushings to prevent individual wires being...

Page 64: ...pen the terminal s operating lever and insert the stripped single conductor into the slot provided in each case as far as it will go Then close the operating lever until it engages NOTE No multi wire...

Page 65: ...suring instrument to check the polarity of the DC cabling Use a suitable measuring instrument to check the voltage max 600 VDC 9 Insert the DC terminals into the respective slot until they engage Fast...

Page 66: ...horised electrical engineer is permitted to connect this equipment to the public grid WARNING Danger due to damaged and or contaminated terminals This can result in serious injury and damage to proper...

Page 67: ...the bat tery to an external point e g switch cab inet In doing so the minimum cross sec tion of the battery s ground conductor must be observed IMPORTANT Before stripping the insulation push the cabl...

Page 68: ...ctor may be connected to each pin The DC cables can be connec ted to the DC terminals without ferrules 5 CAUTION Risk due to overvoltage when using other slots on the terminal This may result in damag...

Page 69: ...crewdriver TX20 and a torque of 1 3 1 5 Nm NOTE Do not use a drill driver as this could cause overturning A possible consequence of overturning is for example damaging the strain relief device IMPORTA...

Page 70: ...y Only trained and qualified personnel are authorised to install and commission the system and only within the scope of the technical regulations The Installation and Operating Instructions must be re...

Page 71: ...TION Danger from faulty or incorrect holes This may lead to injuries to the eyes and hands as a result of flying debris and sharp edges as well as damage to the inverter When drilling wear suitable pr...

Page 72: ...able guide with a step drill 4 Insert the strain relief device into the hole and secure to the torque specified by the manufacturer 5 Guide the mains cable through the strain relief device from below...

Page 73: ...ever until it engages NOTE Only one conductor may be connected to each pin The conductors can be connected without ferrules 7 L1 Phase conductor N Neutral conductor N PEN conductor NOTE The PEN conduc...

Page 74: ...9 Insert the OP terminal into the OP slot until it engages Tighten the union nut of the strain relief device to the torque specified by the manufacturer 74...

Page 75: ...installation commissioning operation or incorrect use This can result in severe personal injury damage to property Only trained and qualified personnel are authorised to install and commission the sys...

Page 76: ...The use of contactor K2 is optional in Australia All pin separation cabling variant e g Germany France Spain Circuit Diagram The Circuit Diagram for the 2 pin double separation e g Germany can be fou...

Page 77: ...backup power network of the inverter from being switched to the public grid The NO contact of relay K3 gives feedback to the inverter on whether the locking was successfully performed by relay K3 The...

Page 78: ...ed again when power returns to the public grid and the backup power network of the inverter from being switched to the public grid The NO contact of relay K3 gives feedback to the inverter on whether...

Page 79: ...is purpose for the main contacts of contactors K4 and K5 This ensures that the ground connection is established as soon as the public grid connection is no longer available The supply voltage for cont...

Page 80: ...gh data transfer of the battery the battery occupies 2 participants If the Inverter control via Modbus function is activated in the Communication Modbus menu no Modbus participants are possible It is...

Page 81: ...nication cables Make sure that you insert the corresponding blanking plugs into any free openings on the sealing insert IMPORTANT Should the blanking plugs be missing or improperly fitted then protect...

Page 82: ...opening 4 Insert the sealing ring between the union nut and the housing opening Press the data cables into the seal s cable guide Then press in the seal until it reaches the underside of the strain r...

Page 83: ...slot IMPORTANT Improperly fitted shielding can cause data communication problems For the wiring proposal recommended by Fronius see page 146 Terminating res istors It may be possible for the system to...

Page 84: ...84...

Page 85: ...ain The WSD switch of the first inverter with connected trigger device in the WSD chain must be in position 1 master The WSD switch of all other inverters should be in the 0 slave position Max distanc...

Page 86: ...e automatic circuit breaker Turn the DC disconnector to the On switch position For systems with a battery observe the switch on sequence according to chapter Suitable battery on page 23 IMPORTANT The...

Page 87: ...app The optical sensor is actuated by touching with a finger The status of the connection is shown via the communication LED To establish the connection carry out the individual steps in the Fronius...

Page 88: ...LAN AP 1x WLAN AP search mode active for 30 minutes Flashing blue The network connection is not configured Lights up yellow The inverter is operating correctly a network fault is indicated Lights up r...

Page 89: ...with the pass word 12345678 4 In the browser address bar enter and confirm the IP address 192 168 250 181 The installation wizard is opened 5 Follow the installation wizard in the individual sections...

Page 90: ...90...

Page 91: ...Settings website of the inverter 91...

Page 92: ...92...

Page 93: ...nd password or go to the User menu and click on the User login button and then log in with your user name and password IMPORTANT Depending on the user s authorization settings can be executed in the i...

Page 94: ...ensure smooth operation in conjunction with other energy producers and in Full Backup backup power mode it is important to install the Fronius Smart Meter at the feed in point The inverter and other...

Page 95: ...tralia Demand Response Mode DRM The pins for control via DRM can be set here Mode Description Information DRM pin I O pin DRM0 Inverter disconnects itself from the grid DRM0 occurs if there is an inte...

Page 96: ...Demand Response Modes DRM Here you can enter a value for the apparent power input and the apparent power output for the Australia country setup 96...

Page 97: ...ed This means that energy can be drawn from the household network and fed into the battery via the Fronius GEN24 Plus inverter You can restrict how much power is consumed by the Fronius GEN24 Plus inv...

Page 98: ...battery no longer being charged or the Ohmpilot no longer being activated An I O is activated or deactivated only after 60 seconds Control Control is deactivated Control is effected by the power gener...

Page 99: ...ctory settings All settings All configuration data is reset with the exception of the country setup Changes to the country setup may only be carried out by authorized personnel All settings with no ne...

Page 100: ...allation work see chapter Closing the inverter s connection area housing cover and commissioning on page 86 2 Connect to the website of the inverter 3 Enter the serial number and verification code VCo...

Page 101: ...d password 7 Drag or upload the service file into the Drop service file here or click to upload field 8 Download the newly generated licence file onto the end device using the Download license file bu...

Page 102: ...and gateway 4 Click on the Connect button The connection is established WLAN Establishing a connection via WPS 1 Click the Enable button 2 Activate WPS on the WLAN router see documentation provided wi...

Page 103: ...t can safeguard a specific number of bits The value 0 or 1 of the parity bit must be cal culated by the sender and is checked by the recipient using the same calculation The parity bit can be calculat...

Page 104: ...the inverter is controlled via Modbus Inverter control includes the following functions On Off Power reduction Specification of a constant power factor cos phi Specification of a constant reactive pow...

Page 105: ...m is limited in accordance with a set power limit If this setting is dis abled the entire available PV power is converted and fed into the grid Total DC system power Input field for the total DC syste...

Page 106: ...figure the primary meter at the feed in point in the Device configuration Components menu area 2 Activate the limit for the entire system in the Safety and grid regulations Export limitation menu area...

Page 107: ...ple 2b Fronius SnapINverter Fronius Primo GEN24 Two primary meters and one secondary meter are required for the inverters The power values shown are an example Inverter configurations with power value...

Page 108: ...Enter the percentage value 50 60 or 70 in the Max grid feed in power input field I O power man agement General In this menu item settings relevant for an electricity company DNO are made An effective...

Page 109: ...nverter and the ripple control signal receiver exceeds 10 m at least a CAT 5 cable is recommended and the shield must be connected at one end to the push in terminal of the data communication area SHI...

Page 110: ...I O power man agement settings 4 relays 110...

Page 111: ...ecommended and the shield must be connected at one end to the push in terminal of the data communication area SHIELD 1 Ripple control signal receiver with 3 relays for effective power limiting 2 I Os...

Page 112: ...I O power man agement settings 3 relays 112...

Page 113: ...commended and the shield must be connected at one end to the push in terminal of the data communication area SHIELD 1 Ripple control signal receiver with 2 relays for effective power limitation 2 I Os...

Page 114: ...I O power man agement settings 2 relays 114...

Page 115: ...ecommended and the shield must be connected at one end to the push in terminal of the data communication area SHIELD 1 Ripple control signal receiver with 1 relay for effective power limiting 2 I Os o...

Page 116: ...various individual tests run automatically one after the other Depending on grid conditions the duration of the test is approx 15 minutes IMPORTANT The inverter may only be commissioned in Italy after...

Page 117: ...t to check the 10 min average voltage in the phases Save as PDF 1 Click the Save as PDF button 2 Enter the file name in the input field and click on the Print button The PDF is created and displayed N...

Page 118: ...118...

Page 119: ...Options 119...

Page 120: ...120...

Page 121: ...the user menu under Notifications as well as in Fronius Solar web In this case the inverter must be repaired by an authorised specialist IMPORTANT The inverter also switches off if the 2 pin signal ca...

Page 122: ...low the safety rules 1 Turn off the automatic circuit breaker Set the DC disconnector to the Off switch position 2 Disconnect connections from the solar module strings Switch off the battery connected...

Page 123: ...20 Then lift the housing cover away from the inverter at the bottom and detach upwards 2 Loosen the five screws of the connection area cover by rotating them 180 to the left using a screwdriver TX20 R...

Page 124: ...stallation already exists 5 Connect the supplied PV PV cables to the respective connections IMPORTANT Note the labelling of the cables when con necting 6 Connect the supplied cables to the respective...

Page 125: ...elines a larger cross section of the ground conductor may be required The use of other inputs can make it difficult to insert the connection area divider or damage the ground conductor 9 Strip the ins...

Page 126: ...Re insert the connection area divider lay the ground conductor in the integ rated cable duct IMPORTANT When inserting the connection area divider s be careful not to kink pinch crush or otherwise dam...

Page 127: ...s observing the labelling 14 Check whether the WSD switch is in posi tion 1 adjust if necessary factory setting position 1 15 Place the cover on the connection area Tighten the five screws by rotating...

Page 128: ...er and tighten the two screws by rotat ing them 180 to the right using a screw driver TX20 Commissioning the inverter 1 Connect the solar module strings Switch on the battery connected to the inverter...

Page 129: ...Appendix 129...

Page 130: ...130...

Page 131: ...grid voltage and DC voltage from solar modules An electric shock can be fatal The connection area must only be opened by an authorised electrician The separate power stage set area must only be opened...

Page 132: ...the housing cover away from the inverter at the bottom and detach upwards 3 Remove any build up of dirt on the heat sink and fan using compressed air a cloth or a brush NOTE Risk due to damage to the...

Page 133: ...rranty Detailed country specific warranty terms are available on the internet www fronius com solar warranty To obtain the full warranty period for your newly installed Fronius inverter or storage sys...

Page 134: ...rs and types are permissible if they are technically and functionally identical to the examples below VMD460 NA D 2 Bender GmbH Co KG RE NA003 M64 Tele Haase Steuerger te Ges m b H K1 and K2 installat...

Page 135: ...k relay RT424012 bracket RT17017 relay base RT78725 K4 and K5 installation contactor Number of NC contacts 2 25 A Coil voltage 230 V AC 2P Nominal frequency 50 60 Hz Coil fuse 6 A Min short circuit cu...

Page 136: ...f the SPD surge protective device is triggered the inverter must be repaired by an authorised specialist Install the bypass ex works or a trigger device Set the WSD Wired Shut Down switch to position...

Page 137: ...ber of inputs PV1 2 Number of inputs PV2 2 DC input data battery Max voltage 455 V Min voltage 150 V Max current 22 A Max output 3000 W 3680 W 4000 W DC inputs 1 DC overvoltage category in accordance...

Page 138: ...4000 W Nominal output power per phase 7 3680 W Nominal output current per phase 16 A Nominal grid voltage 3 NPE 220 V 380 V 3 NPE 230 V 400 V Nominal frequency for Full Backup 53 63 Hz 1 Switchover ti...

Page 139: ...Spec 2x RS485 2 wire Voltage level of digital inputs low min 0 V max 1 8 V high min 4 5 V max 28 8 V Input currents of digital inputs depending on the input voltage input resistance 70 kOhm Total powe...

Page 140: ...ax output current 27 5 A Starting current 6 20 A 1 3 ms Nominal frequency 50 60 Hz 1 Nominal frequency for Full Backup 53 63 Hz 1 Total harmonic distortion 3 5 Power factor cos phi 2 0 8 1 adjustable...

Page 141: ...ons H x W x D 528 474 163 mm Weight 15 4 kg Permissible ambient temperature 40 C 60 C Permissible humidity 0 100 incl condensation EMC device class B DC AC overvoltage category 2 3 Pollution degree 2...

Page 142: ...Explanation of footnotes 1 The values stated are defaults the inverter is configured specifically to suit the requirements of the relevant country 2 Depending on the country setup or device specific s...

Page 143: ...Circuit diagrams 143...

Page 144: ...144...

Page 145: ...Circuit Diagram PV Point OP Circuit Diagram 145 EN...

Page 146: ...Fronius Primo GEN24 and BYD Battery Box Premium HV Circuit Diagram 146...

Page 147: ...Automatic switch to backup power 1 pin double separation e g Austria Circuit Diagram 147 EN...

Page 148: ...Automatic switch to backup power 1 pin single separation e g Australia Circuit Diagram 148...

Page 149: ...Automatic switch to backup power 2 pin double separation e g Germany Circuit Diagram 149 EN...

Page 150: ...Automatic switch to backup power 2 pin single separation e g France Spain Circuit Diagram 150...

Page 151: ...Automatic switch to backup power 2 pin double separation e g UK Circuit Diagram 151 EN...

Page 152: ...Automatic switch to backup power 2 pin double separation with ext grid and system protection e g Italy Circuit Diagram 152...

Page 153: ...Fronius Primo GEN24 with Enwitec Box Circuit Diagram 153 EN...

Page 154: ...Wiring diagram surge protective device SPD Circuit Diagram 154...

Page 155: ...Dimensions of the inverter 155...

Page 156: ...156...

Page 157: ...Fronius Primo GEN24 3 6 kW Fronius Primo GEN24 3 6 kW 157 EN...

Page 158: ...158...

Page 159: ...159 EN...

Page 160: ...INTERNATIONAL GMBH Froniusstra e 1 A 4643 Pettenbach AUSTRIA contact fronius com www fronius com Under www fronius com contact you will find the addresses of all Fronius Sales Service Partners and lo...

Reviews: