![Froling PE1 Pellet Installation Instructions Manual Download Page 27](http://html1.mh-extra.com/html/froling/pe1-pellet/pe1-pellet_installation-instructions-manual_2338712027.webp)
Description
PE1 Pellet 15
PE1 Pellet 20
Test book number
PB0730015
PB0740015
Test data - Emissions in [mg/MJ]
1)
(nominal load/partial load)
Carbon monoxide (CO)
mg/MJ
11 / 11
10 / 11
Nitrogen oxide (NOx)
mg/MJ
84 / 72
85 / 72
Organic hydrocarbons (OGC)
mg/MJ
0.5 / 0.4
0.4 / 0.4
Dust
mg/MJ
8.2 / 3.8
9.1 / 3.8
Boiler efficiency
%
94.7 / 91.1
95.0 / 91.1
1.The pollutant concentration is specified as a mass based on the energy content of the fuel fed to the combustion system in mg/MJ
Test data - Emissions in [mg/m³]
1)
(nominal load/partial load)
Carbon monoxide (CO)
mg/m³
17 / 17
15 / 17
Nitrogen oxide (NOx)
mg/m³
129 / 110
131 / 110
Organic hydrocarbons (OGC)
mg/m³
0.7 / 0.6
0.7 / 0.6
Dust
mg/m³
12.7 / 5.8
14.0 / 5.8
Boiler efficiency
%
94.7 / 91.1
95.0 / 91.1
1.Emissions values based on dry flue gas at standard temperature and pressure (0°C, 1013 mbar) with a volume content of oxygen of 13%
Test report data
Technology
3
Technical specifications
Installation Instructions PE1 Pellet 7-35 | M1441017_en
27