Tstat Series
- 52 -
Address
Register Name
Register and Description
575
MODBUS_DISP_ITEM_AI8
Decide which item will be shown in the display sequency.see up note
576
MODBUS_DISP_ITEM_MODE
Decide which item will be shown in the display sequency.see up note
577
MODBUS_DISP_ITEM_USER_INFO Decide which item will be shown in the display sequency.see up note
578
MODBUS_DISP_ITEM_CLOCK_
DATE
Decide which item will be shown in the display sequency.see up note
579
MODBUS_DISP_ITEM_CLOCK_
TIME
Decide which item will be shown in the display sequency.see up note
580
MODBUS_DISP_ITEM_EXTENAL_
SENSOR1
Decide which item will be shown in the display sequency.see up note
581
MODBUS_DISP_ITEM_EXTENAL_
SENSOR2
Decide which item will be shown in the display sequency.see up note
582
MODBUS_DISP_ITEM_EXTENAL_
SENSOR3
Decide which item will be shown in the display sequency.see up note
583
MODBUS_DISP_ITEM_EXTENAL_
SENSOR4
Decide which item will be shown in the display sequency.see up note
584
MODBUS_DISP_ITEM_OUT1
Decide which item will be shown as the output item.
585
MODBUS_DISP_ITEM_OUT2
Decide which item will be shown as the output item.
586
MODBUS_DISP_ITEM_OUT3
Decide which item will be shown as the output item.
587
MODBUS_DISP_ITEM_OUT4
Decide which item will be shown as the output item.
588
MODBUS_DISP_ITEM_OUT5
Decide which item will be shown as the output item.
589
MODBUS_DISP_ITEM_OUT6
Decide which item will be shown as the output item.
590
MODBUS_DISP_ITEM_OUT7
Decide which item will be shown as the output item.
591
MODBUS_OUTPUT_PWM_AUTO_
COAST
"PWM output range in COAST mode. 0 = CLOSE, 1 = OPEN, 2 = 0-100%, 3 =
50-100%,
4 = 0-50%. MSb 4 bits correspond to output4 and LSB 4 bits correspond to out-
put5"
592
MODBUS_OUTPUT_PWM_AUTO_
COOL1
"PWM output range in COOLING1 mode. 0 = CLOSE, 1 = OPEN, 2 = 0-100%, 3
= 50-100%,
4 = 0-50%. MSb 4 bits correspond to output4 and LSB 4 bits correspond to out-
put5"
593
MODBUS_OUTPUT_PWM_AUTO_
COOL2
"PWM output range in COOLING2 mode. 0 = CLOSE, 1 = OPEN, 2 = 0-100%, 3
= 50-100%,
4 = 0-50%. MSb 4 bits correspond to output4 and LSB 4 bits correspond to out-
put5"
594
MODBUS_OUTPUT_PWM_AUTO_
COOL3
"PWM output range in COOLING3 mode. 0 = CLOSE, 1 = OPEN, 2 = 0-100%, 3
= 50-100%,
4 = 0-50%. MSb 4 bits correspond to output4 and LSB 4 bits correspond to out-
put5"
595
MODBUS_OUTPUT_PWM_AUTO_
HEAT1
"PWM output range in HEATING1 mode. 0 = CLOSE, 1 = OPEN, 2 = 0-100%, 3 =
50-100%,
4 = 0-50%. MSb 4 bits correspond to output4 and LSB 4 bits correspond to out-
put5"
596
MODBUS_OUTPUT_PWM_AUTO_
HEAT2
"PWM output range in HEATING2 mode. 0 = CLOSE, 1 = OPEN, 2 = 0-100%, 3 =
50-100%,
4 = 0-50%. MSb 4 bits correspond to output4 and LSB 4 bits correspond to out-
put5"
597
MODBUS_OUTPUT_PWM_AUTO_
HEAT3
"PWM output range in HEATING3 mode. 0 = CLOSE, 1 = OPEN, 2 = 0-100%, 3 =
50-100%,
4 = 0-50%. MSb 4 bits correspond to output4 and LSB 4 bits correspond to out-
put5"
Summary of Contents for Tstat Series
Page 6: ...Tstat Series 6 ...
Page 7: ...Tstat Series 7 ...
Page 8: ...Tstat Series 8 Switching Time Measurement Circuit and Waveforms ...
Page 9: ...Tstat Series 9 Tstat6 Highlights ...
Page 10: ...Tstat Series 10 Tstat6 Jumper Settings Tstat6 Wiring Diagram ...
Page 11: ...Tstat Series 11 Tstat6 CO2 Highlights Tstat6 CO2 Jumper Settings ...
Page 12: ...Tstat Series 12 Tstat6 CO2 Wiring Diagram ...
Page 13: ...Tstat Series 13 Tstat6 Zigbee Highlights ...
Page 14: ...Tstat Series 14 Tstat6 Zigbee Jumper Settings Tstat6 Zigbee Wiring Diagram ...
Page 15: ...Tstat Series 15 Tstat6 OCC Highlights ...
Page 16: ...Tstat Series 16 Tstat6 OCC Jumper Settings Tstat6 OCC Wiring Diagram ...
Page 26: ...Tstat Series 26 ...