Tstat Series
- 44 -
Address
Register Name
Register and Description
346
MODBUS_DAY_COOLING_DEADBAND
(Day)Occupied cooling setpoint dead band , offset from setpoint for
cooling to begin. Units are 0.1 deg.
347
MODBUS_DAY_HEATING_DEADBAND
(Day)Occupied heating setpoint dead band , offset from setpoint for
heating to begin. Units are 0.1 deg.
348
MODBUS_DAY_COOLING_SETPOINT
(Day)Occupied cooling setpoint (day cooling setpoint)
349
MODBUS_DAY_HEATING_SETPOINT
(Day)Occupied heating setpoint (day heating setpoint)
350
MODBUS_NIGHT_SETPOINT
(Night)Unoccupied setpoin.
351
MODBUS_APPLICATION
Spare
352
MODBUS_NIGHT_HEATING_DEADBAND
(Night)Unoccupied heating setpoint dead band , heating deadband
for the night (OFF) mode. Units of 1 deg.
353
MODBUS_NIGHT_COOLING_DEADBAND
(Night)Unoccupied cooling setpoint dead band , cooling deadband
for the night (OFF) mode. Units of 1 deg.
354
MODBUS_NIGHT_HEATING_SETPOINT
(Night)Unoccupied heating setpoint
355
MODBUS_NIGHT_COOLING_SETPOINT
(Night)Unoccupied cooling setpoint
356
MODBUS_WINDOW_INTERLOCK_COOLING_
SETPOINT
(TBD)Window interlock cooling setpoint
357
MODBUS_WINDOW_INTERLOCK_HEATING_
SETPOINT
(TBD)Window interlock heating setpoint
358
MODBUS_UNIVERSAL_NIGHTSET
PID2 Unoccupied (OFF) Setpoint
359
MODBUS_UNIVERSAL_SET
PID2 Occupied Setpoint
360
MODBUS_UNIVERSAL_DB_HI
PID2 Heating Deadband TBD: can write to either deadband or to
setpoint
361
MODBUS_UNIVERSAL_DB_LO
PID2 Cooling Deadband, TBD: can write to either deadband or to
setpoint
362
MODBUS_ECOMONY_COOLING_SETPOINT
Economy mode cooling setpoint
363
MODBUS_ECOMONY_HEATING_SETPOINT
Economy mode heating setpoint
364
MODBUS_POWERUP_SETPOINT
POWERUP_SETPOINT , setpoint on power up
365
MODBUS_MAX_SETPOINT
MAX_SETPOINT, Setpoint high, the highest setpoint a user will be
able to set from the keypad.
366
MODBUS_MIN_SETPOINT
MIN_SETPOINT, Setpoint Low, the lowest setpoint a user will be
able to set from the keypad.
367
MODBUS_MAX_SETPOINT2
Reserved,MAX_SETPOINT2
368
MODBUS_MIN_SETPOINT2
Reserved,MIN_SETPOINT2
369
MODBUS_MAX_SETPOINT3
Reserved,MAX_SETPOINT3
370
MODBUS_MIN_SETPOINT3
Reserved,MIN_SETPOINT3
371
MODBUS_MAX_SETPOINT4
Reserved,MAX_SETPOINT4
372
MODBUS_MIN_SETPOINT4
Reserved,MIN_SETPOINT4
373
MODBUS_SETPOINT_INCREASE
Setpoint increment on the display each time the user hits the up/
down buttons. Units are 0.1Deg, 10 = 1Deg and so on.
374
MODBUS_FREEZE_TEMP_SETPOINT
"Freeze protect setpoint. If the ambient temperature less than the
setpoint,
the heating valve will open some time the Delay to off register set ."
375
MODBUS_WALL_SETPOINT
Reserved, wall setpoint
376
MODBUS_CEILING_SETPOINT
Reserved,ceiling setpoint
377
MODBUS_AVERAGE_SETPOINT
Reserved,average setpoint
378
MODBUS_UNOCCUPIED_HEATING
Reserved,unoccupied heating
Summary of Contents for Tstat Series
Page 6: ...Tstat Series 6 ...
Page 7: ...Tstat Series 7 ...
Page 8: ...Tstat Series 8 Switching Time Measurement Circuit and Waveforms ...
Page 9: ...Tstat Series 9 Tstat6 Highlights ...
Page 10: ...Tstat Series 10 Tstat6 Jumper Settings Tstat6 Wiring Diagram ...
Page 11: ...Tstat Series 11 Tstat6 CO2 Highlights Tstat6 CO2 Jumper Settings ...
Page 12: ...Tstat Series 12 Tstat6 CO2 Wiring Diagram ...
Page 13: ...Tstat Series 13 Tstat6 Zigbee Highlights ...
Page 14: ...Tstat Series 14 Tstat6 Zigbee Jumper Settings Tstat6 Zigbee Wiring Diagram ...
Page 15: ...Tstat Series 15 Tstat6 OCC Highlights ...
Page 16: ...Tstat Series 16 Tstat6 OCC Jumper Settings Tstat6 OCC Wiring Diagram ...
Page 26: ...Tstat Series 26 ...
Page 31: ...Tstat Series 31 ...