Tstat Series
- 41 -
Address
Register Name
Register and Description
254
MODBUS_OUTPUT_MANU_EN-
ABLE
Auto Manual mode for outputs, bit 0 = relay1, bit1 = relay2… bit 5 = (out6) analog-
out1, bit6 = (out7) analogout2. In manual mode you can write to the output registers
for debugging or from an external master to override the local PID logic.
255
MODBUS_MANU_RELAY1
Not used
256
MODBUS_MANU_RELAY2
Not used
257
MODBUS_MANU_RELAY3
Not used
258
MODBUS_MANU_RELAY4
Not used
259
MODBUS_MANU_RELAY5
Not used
260
MODBUS_MANUAL_AO1
Not used
261
MODBUS_MANUAL_AO2
Not used
262
MODBUS_DEADMASTER_AUTO_
MANUAL
"DEADMASTER_MODE = 0, the default, outputs will not change when deadmaster
is triggered
DEADMASTER_MODE = 1, the output will be trigger to “AUTO” mode if they were
previously in manual
DEADMASTER_MODE = 2, the outputs will go to manual on or off as de
fi
ned in the
following registers."
263
MODBUS_DEADMASTER_OUT-
PUT_STATE
"De
fi
ne output states when DEADMASTER_MODE = 2 (active)
Bit0 is for relay 1, bit1 for relay 2 and so on up to output 5"
264
MODBUS_DEADMASTER_COOL_
OUTPUT
Analog Output1 goes to this value when DEADMASTER_MODE = 2 (active),
0-1000
265
MODBUS_DEADMASTER_HEAT_
OUTPUT
Analog Output2 goes to this value when DEADMASTER_MODE = 2 (active),
0-1000
266
MODBUS_OUTPUT1_FUNCTION
"Output1 Function setting:
0=normal, default. 1 = rotation (old disabled feature) 2 = lighting control, one key-
pad button can be assigned to toggle a relay on & off "
267
MODBUS_OUTPUT2_FUNCTION
Output2 function setting (see above)
268
MODBUS_OUTPUT3_FUNCTION
Output3 function setting (see above)
269
MODBUS_OUTPUT4_FUNCTION
Output4 function setting (see above)
270
MODBUS_OUTPUT5_FUNCTION
Output5 function setting (see above)
271
MODBUS_OUTPUT6_FUNCTION
(future)Output6 function setting (see above)
272
MODBUS_OUTPUT7_FUNCTION
(future)Output7 function setting (see above)
273
MODBUS_FAN_SPEED
"FAN_SPEED, current operating fan speed Relay Output Tables (bit0 = relay1,
bit1 = relay2, bit2 = relay3, bit3 = relay4, bit4 = relay5) Fan0 table is for the off
state. Fan1, Fan2, and Fan3 are for the manual states.
Fan4 is for the Auto state. These states are controlled by the user. The mode of
operation (coasting, cooling, heating) is determined by the PID parameter."
274
MODBUS_PID_OUTPUT1
Output 1 PID Interlock 0 = PID1, can assign each output to either PID1
or 2, the max or the min of the two PIDS
275
MODBUS_PID_OUTPUT2
Output 2 PID Interlock 1 = PID2
276
MODBUS_PID_OUTPUT3
Output 3 PID Interlock 2 = Maximum of PID1 and PID2
277
MODBUS_PID_OUTPUT4
Output 4 PID Interlock 3 = Minimum of PID1 and PID2
278
MODBUS_PID_OUTPUT5
Output 5 PID Interlock
279
MODBUS_PID_OUTPUT6
Output 6 PID Interlock
280
MODBUS_PID_OUTPUT7
Output 7 PID Interlock
281
MODBUS_UNIVERSAL_OUT-
PUT_BEGIN
PID2 Output table- Coasting
282
MODBUS_UNIVERSAL_OUT-
PUT_COOL1
PID2 Output table- Cooling1
Summary of Contents for Tstat Series
Page 6: ...Tstat Series 6 ...
Page 7: ...Tstat Series 7 ...
Page 8: ...Tstat Series 8 Switching Time Measurement Circuit and Waveforms ...
Page 9: ...Tstat Series 9 Tstat6 Highlights ...
Page 10: ...Tstat Series 10 Tstat6 Jumper Settings Tstat6 Wiring Diagram ...
Page 11: ...Tstat Series 11 Tstat6 CO2 Highlights Tstat6 CO2 Jumper Settings ...
Page 12: ...Tstat Series 12 Tstat6 CO2 Wiring Diagram ...
Page 13: ...Tstat Series 13 Tstat6 Zigbee Highlights ...
Page 14: ...Tstat Series 14 Tstat6 Zigbee Jumper Settings Tstat6 Zigbee Wiring Diagram ...
Page 15: ...Tstat Series 15 Tstat6 OCC Highlights ...
Page 16: ...Tstat Series 16 Tstat6 OCC Jumper Settings Tstat6 OCC Wiring Diagram ...
Page 26: ...Tstat Series 26 ...
Page 31: ...Tstat Series 31 ...