Tstat Series
- 20 -
Code
Description (Range, Default)
Hdb
Cdb
Heating & Cooling Deadbands (1-200, 10)
If there is one setpoint, the heating setpoint follows the cooling setpoint and is calculated by:
Heating Setpoint = Setpoint - Heating Deadband.
Cooling Setpoint = Se Cooling Deadband
If there are two setpoints, heating and cooling are separately adjusted. The setpoints are calculated as follows:
Heating Setpoint = Max( Cooling Se Cooling Deadband , Heating Setpoint )
Cooling Setpoint = Min( Cooling Setpoint, Heating Setpoint - Cooling Deadband)
The min value for Cdb is 1.0° (C or F) to ensure that simultaneous heating and cooling is never allowed. The maximum value is arbitrarily
set to 20.0°. The deadband values are in increments of 0.1° (i.e. 20 means 2.0°) and are in the same units (C or F) as the tstat.
UNITS
Degrees C/Degrees F (0-1, - )
The display can be switched to show Degrees C or Degrees F. 0 = C, 1 = F.
FAn
Number of Fan Speeds to show on the display (0-3, 3)
The number of fan speeds allowed. Fan = 3, user will see “Off, -1-, -2-, -3-, Aut” Fan = 2, user will see “Off, -1-, -2-, Aut” Fan = 1, user will
see “Off, -1- , Aut” , Fan = 0, user will see “Off, On”
nHd
Night Heating Deadband (0-35, 10) for deg C, (0-95, 10) for deg F
nCd
Night Cooling Deadband (0-99, 10) for deg C and F
When the tstat is in unoccupied mode, and APP is set to 0, the heating setpoint is adjusted downwards by the amount of the nHd. The
cooling setpoint is adjusted upwareds by the amount of nCd. The night deadband values are in increments of 1° (i.e. 10 means 10°) and
are in the same units (C or F) as the tstat.
Note: The night heating setpoint is prevented through an internal software interlock from being set below 5°C, regardless of the user heat-
ing setpoint and the value stored in NHS.
nSp
APP
Application (0-1, 0)
0 - OFFICE applications mode
The night time setpoints are speci
fi
ed value
Night Heating Setpoint = nHS value.
Night Cooling Setpoint = nCS value.
1 - HOTEL or RESIDENTIAL applications mode
The night time setpoints are a speci
fi
ed deadband in relation with the day time setpoints
Night Heating Setpoint = Cooling Setpoint - nHd value.
Night Cooling Setpoint = Cooling Se nCd value.
POS
Power on setpoint (0-255, 20) for deg C, (0-255, 68) for deg F
Certain applications require the thermostat to power up with a known setpoint that is stored through a power outage. This feature is useful
in some of the transducer modes where the central DDC controller can cycle the power to the thermostats to reset the room setpoints to a
known value every day. The power on setpoint value is in increments of 1° (i.e. 20 means 20°) and is in the same units (C or F) as the tstat.
POn
Power on Mode (0-3, 3)
This setting allows the thermostat to power up in one of three modes: 0 = power off, 1 = power up in on mode, 2 = last value (default), 3 =
auto mode. The on and off settings are self explanatory and are useful in certain DDC applications where the central controller can cycle
the power to each thermostat to sweep them off each evening for example. The default value is “last value” and will cause the thermostat
to power up in whatever state it was in before the power outage.
Summary of Contents for Tstat Series
Page 6: ...Tstat Series 6 ...
Page 7: ...Tstat Series 7 ...
Page 8: ...Tstat Series 8 Switching Time Measurement Circuit and Waveforms ...
Page 9: ...Tstat Series 9 Tstat6 Highlights ...
Page 10: ...Tstat Series 10 Tstat6 Jumper Settings Tstat6 Wiring Diagram ...
Page 11: ...Tstat Series 11 Tstat6 CO2 Highlights Tstat6 CO2 Jumper Settings ...
Page 12: ...Tstat Series 12 Tstat6 CO2 Wiring Diagram ...
Page 13: ...Tstat Series 13 Tstat6 Zigbee Highlights ...
Page 14: ...Tstat Series 14 Tstat6 Zigbee Jumper Settings Tstat6 Zigbee Wiring Diagram ...
Page 15: ...Tstat Series 15 Tstat6 OCC Highlights ...
Page 16: ...Tstat Series 16 Tstat6 OCC Jumper Settings Tstat6 OCC Wiring Diagram ...
Page 26: ...Tstat Series 26 ...
Page 31: ...Tstat Series 31 ...