S90-510 CS (MAR 07) FRICK
®
QUANTUM™ LX AcuAir
®
CONTROL PANEL
Page 76
COMMUNICATIONS SETUP
SETPOINT VALUES: (Continued)
Frick
®
Address
AB
Address
Modbus
Address
Description of Data
8305
N113:05 48306
Regen Burner Start Delay
8306
N113:06 48307
Regen Burner Ramp Time
8307
N113:07 48308
False Regen Burner Status Input Delay
8308
N113:08 48309
Regen Burner Safeties Shutdown Delay
8309
N113:09 48310
Regen Burner Flame Failure Warning Delay
8320
N113:20 48321
No Regen Air Flow Shutdown Delay - Starting
8321
N113:21 48322
No Regen Air Flow Shutdown Delay - Running
8322
N113:22 48323
False Regen Air Flow Input Delay
8323
N113:23 48324
Desiccant Wheel Confirm Input Delay
COMMANDS:
Frick
®
Address
AB
Address
Modbus
Address
Read/Write Description of Data
Value Codes
8910
N119:10
49011
W
Remote - Start
1 = Start
8911
N119:11
49012
W
Remote - Stop
1 = Stop
8915
N119:15
49016
W
Remote – Unit Mode
0 = Process 1
1 = Process 2
2 = Cleanup
8917
N119:17
49018
W
Remote - Clear Alarms
1 = Clear Alarms
8920
N119:20
49021
W
Remote – Communications Units
0 = Celsius, PSIA
1 = Panel Units
GENERAL NOTES:
•
Command Values need tenths field added. For example, to start the Air Handler, the table above states that 1 = Start. However,
being that one decimal place is assumed, a value of 10 actually needs to be sent.