S90-510 CS (MAR 07) FRICK
®
QUANTUM™ LX AcuAir
®
CONTROL PANEL
Page 48
COMMUNICATIONS SETUP
MODE VALUES: (Read Only)
Frick
®
Address
AB
Address
Modbus
Address
Description of Data
Value Codes
4076
N40:76
44077 Date Format (Local Display Only)
0 = US
1 = Europe
4080
N40:80
44081 Manual Status Selection
0 = Off
1 = Running
10 = Idle
4081
N40:81
44082 Remote Status Setting
0 = Off
1 = Running
4082 N40:82 44083
Status
Source
Flag
0 = Button
1 = Digital Input
2 = Schedule
3 = Shutdown
4083
N40:83
44084 Manual Mode Selection
0 = Process 1
1 = Process 2
2 = Cleanup
10 = Idle
4084 N40:84 44085
Remote
Mode
Setting
0 = Process 1
1 = Process 2
2 = Cleanup
4085 N40:85 44086
Mode
Source
Flag
0 = Button
1 = Digital Input
2 = Schedule
4086
N40:86
44087 Manual Defrost Selection
1 = Start Defrost
10 = Idle
4087
N40:87
44088 Defrost Source Flag
0 = None
1 = Defrost Button
2 = Digital Input
3 = Defrost Schedule
4 = Liquid Counter
5 = Differential Pressure
4089
N40:89
44090 Defrost Hot Gas Flag
0 = False
1 = Hot Gas in Coil
2 = Startup Bleed
4090
N40:90
44091 Desiccant Confirm Flag
0 = Normal
1 = Failed
4091
N40:91
44092 Desiccant Confirm Status
0 = Off
1 = On
4092
N40:92
44093 Regen Burner Control Flag
0 = Humidity
1 = Pre-Wheel Regen Temp
2 = Post-Wheel Regen Temp