S90-510 CS (MAR 07) FRICK
®
QUANTUM™ LX AcuAir
®
CONTROL PANEL
Page 20
COMMUNICATIONS SETUP
CHANGE STATUS COMMAND: $IDCU
$
Start of command sequence.
ID
AcuAir ID code.
CU
Set Mode to Clean Up
CS
Checksum
CR
Carriage Return
RETURNED ANSWER, “A” followed by the “ID”,
And 1 “CR”, “LF” if successful.
And 0 “CR”, “LF” if unsuccessful.
NOTE: The commands P1, P2 and CU commands
can be used to set the current AcuAir
®
mode.
RETURN DATA VALUE FROM TABLE
$IDT1
$
Start of command sequence.
ID
AcuAir ID code.
T1
Return the value of a Table address.
0000
Frick Address of first data value in Table
00
Number of subsequent values to return
(up to 25 values can be requested)
CS
Checksum
CR
Carriage Return
RETURNED ANSWER,
Starting
Character
Position
Description of returned data
1
“A” Acknowledge
2
“01” AcuAir ID code.
4
Value(s) of requested data.
CS (Checksum followed by Carriage return,
Line feed.)
CHANGE SETPOINT COMMAND: $IDCS
$
Start of command sequence.
ID
AcuAir ID code.
CS
Change Table address’s setpoint value.
0000
Frick Table address of the setpoint.
0000000
00
New setpoint scaled x100.
CS
Checksum
CR
Carriage Return
RETURNED ANSWER, “A” followed by the “ID”,
and 1 “CR”, “LF” if successful.
and 0 “CR”, “LF” if unsuccessful.
RETURN Unit Status – Unit data: $01Z1
$
Start of command sequence.
01
AcuAir ID code.
Z1
Unit Status Command
CS
Checksum
CR
Carriage Return
RETURNED ANSWER,
A
Acknowledge
01
AcuAir ID code.
Z1
Unit Status Command
F
Digital Inputs
F
Digital Inputs
F
Digital Outputs
F
Digital Outputs
F
Digital Outputs
F
Digital Outputs
000
Outside/Return Air Dampers
000
Exhaust Command
000
Burner Output
000
Heat Profile
+000
Outside Air Temperature
+000
Discharge Air Temp.
+000
Room/Return Air Temp
+000
Spare Temperature
000
Damper Position
000
Exhaust Fan 1 Position
000
Exhaust Fan 2 Position
00000
Ammonia Detector
000
Humidity
+000
Room Pressure Sensor
+000
Pre-Heat Air Temp.
0
Unit Status: 0-Off; 1-Running; 2-Starting
0
Unit Air Handling Mode:0-Process; 1-Cleanup
0
Unit Control Mode: 0-Local; 1-Remote
0
Control Value: 0-None; 1-Return Air; etc.
0
Control Setpoint: 0-None; 1-Process; etc.
0
Alarm: 0-None; 1-Alarm; 2-Shutdown
CS Checksum
CR
Carriage Return