S90-510 CS (MAR 07) FRICK
®
QUANTUM™ LX AcuAir
®
CONTROL PANEL
Page 26
COMMUNICATIONS SETUP
Message Read Logic
Use the following logic to read data from the
Quantum™ panel. To read more data or to read data
from several compressors, copy / paste these rungs
as needed then modify the control block and setup
screen parameters accordingly. The following
message read instruction will be executed whenever
counter 5:0 (logic shown above) is equal to 0.
Delay Between Messages
The delay timer on rung 3 must be used when
communicating to the Quantum™ LX with the 100ms
preset as shown. This time delay may be decreased
when communicating to more than one compressor
provided the messages are alternated between
compressors.