FRICK
®
QUANTUM™ LX AcuAir
®
CONTROL PANEL
S90-510 CS (MAR 07)
COMMUNICATIONS SETUP
Page 23
Message Retries: 3
Parity: None
Station Address (Source ID): 5 (
Leader
DF1
selected ID#)
Error Detect: BCC / CRC
RTS off Delay (x20ms): 0
RTS Send Delay (x20ms): 0
Pre-Send Time Delay (x1 ms): 0
Control Line: No Handshaking
Polling Mode: Message Based (do not allow
follower
to initiate messages)
Priority Polling Range - Low: 255, High: 0
Normal Polling Range - Low: 255, High: 0
Normal Poll Group Size: 0
Reply Message Wait Time (x20ms): 20
System Mode Driver: DF1 Half-Duplex
Leader
or DF1 Full-Duplex
User Mode Driver: Generic ASCII
Write Protect: DISABLED
Mode Changes: DISABLED
Mode Attention Character: \0x1b (default)
System Mode Character: S (default)
User Mode Character: U (default)
Edit Resource/File Owner Timeout (Sec): 60
Passthru Link ID (decimal): 1
Read Message Setup Example
Read/Write Message
Type: Peer-To-Peer
Read/Write: Read
Target Device: 500 CPU
Local/Remote: Local
Control Block: N11:0
Control Block Length: 14
Channel: 0
Target Node: 2 (002) (this is the Quantum™
Panel ID)
Local File Address: N12:0
Target File Address/Offset: N10:0
Message Length in Elements: 50
Message Time-out (seconds): 15
(Refer to the Allen-Bradley Programming
Overview Section for more information)
Write Message Setup Example
Read/Write Message
Type: Peer-To-Peer
Read/Write: Write
Target Device: 500 CPU
Local/Remote: Local
Control Block: N11:0
Control Block Length: 14
Channel: 0
Target Node: 2 (002) (this is the Quantum™
Panel ID)
Local File Address: N12:0
Target File Address/Offset: N55:3
Message Length in Elements: 1
Message Time-out (seconds): 15
Enter 20 into N12:0 to send the command to set
the compressor in remote mode.
(Refer to the Allen-Bradley Programming
Overview Section for more information)
PLC-5/30 - Suggested Setup
Channel 0 - 25-pin D-shell serial port; supports
standard EIA RS-232C and RS-423 and is RS-422A
compatible.
NOTE: Channel 0 is optically-coupled (provides high
electrical noise immunity) and can be used with most
RS-422A equipment as long as:
•
Termination resistors are not used
•
The distance and transmission rate are
reduced to comply with RS-423
requirements
The PLC-5’s switch 2 is used to select RS-232C, RS-
422A, or RS-423. Channel 0 can be wired for RS-422.
Following is the pin connections showing how to wire
the PLC-5 channel 0 connector to the Quantum™ for
RS-422 communication:
PLC-5 CH0
Quantum™ Com-2
Pin 2 (TXD.OUT+)
Pin 1 (-RX)
Pin 3 (RXD.IN+)
Pin 3 (-TX)
Pin 14 (TXD.OUT-)
Pin 2 (+RX)
Pin 16 (RXD.IN-)
Pin 4 (+TX)
Channel 0 Setup:
Port
Maximum Cable length
RS-232C
15 m (50 ft)
RS-422A
61 m (200 ft)
RS-423
61 m (200 ft)
Important guidelines:
•
When channel 0 is configured for RS-422A
compatibility, do not use terminating
resistors anywhere on the link.
•
When channel 0 is configured for RS-422A
(compatible) and RS-423, do not go beyond
61 m (200 ft). This distance restriction is
independent from the transmission rate.
Channel Configuration
Channel 0 = System (
Leader
) for half-duplex
or System (Point-To-Point) for full-duplex
Remote Mode Change: DISABLED
Mode attention Char: \0x1b
System mode char: S
User mode char: U
Baud rate: 19200 (suggested)
Stop bits: 1
Parity: None
Station address: 5 (this devices ID#)
Control line: No Handshaking
Reply Msg Wait (20ms):
ACK timeout (20ms):
DF1 retries: 3
Msg appl timeout (30 secs):2