FRICK
®
QUANTUM™ LX AcuAir
®
CONTROL PANEL S90-510 CS (MAR 07)
COMMUNICATIONS SETUP Page 39
A new dialog box will be shown asking to select a Com
port (choose the Com port that your communications cable
is attached to, this will normally be Com-1). The phone
number box should be blank. Click on [OK].
The Com-1 properties dialog box will now appear. The
parameters in this box must match the requirements of the
protocol that you are wishing to use. The one box that
normally would need to be changed from one protocol to
the next is the Data Bits box. For MODBUS
®
ASCII, you
can use either 7 or 8 data bits, for Frick
®
and Quantum™
protocols, use only 8 data bits.
NOTE: Allen-Bradley, MODBUS
®
RTU and TCP/IP
protocols cannot be tested using Hyperterminal.
For the purpose of this document, Frick
®
# protocol will be
used. Refer to the MODBUS
®
ASCII section of this manual
for information on MODBUS
®
.
Set the five boxes as follows, then click [OK].
•
Bits per second: 9600 (must match the
Quantum™)
•
Data bits: 8
•
Parity: None
•
Stop Bits: 1
•
Flow Control: None