S90-510 CS (MAR 07) FRICK
®
QUANTUM™ LX AcuAir
®
CONTROL PANEL
Page 56
COMMUNICATIONS SETUP
MODE VALUES: (Read Only)
Frick
®
Address
AB
Address
Modbus
Address
Description of Data
Value Codes
4251
N42:51
44252 PI 5 Control
0 = Disabled
1 = Running
2 = Always
4252
N42:52
44253 PI 5 Action
0 = Forward
1 = Reverse
4253
N42:53
44254 PI 5 Control Point
0 = Outside Air Temperature
1 = Discharge Air Temperature
2 = Room Air Temperature
3 = Return Air Temperature
4 = Pre-Coil Air Temperature
5 = Coil Air Temperature
6 = Room Air Humidity
7 = Room Pressure
9 = Outside Air Damper
31 = User defined analog input #1
32 = User defined analog input #2
33 = User defined analog input #3
34 = User defined analog input #4
35 = User defined analog input #5
36 = User defined analog input #6
37 = User defined analog input #7
38 = User defined analog input #8
39 = User defined analog input #9
40 = User defined analog input #10
41 = User defined analog input #11
42 = User defined analog input #12
43 = User defined analog input #13
44 = User defined analog input #14
45 = User defined analog input #15
46 = User defined analog input #16
47 = User defined analog input #17
48 = User defined analog input #18
49 = User defined analog input #19
50 = User defined analog input #20