S90-510 CS (MAR 07) FRICK
®
QUANTUM™ LX AcuAir
®
CONTROL PANEL
Page 50
COMMUNICATIONS SETUP
MODE VALUES: (Read Only)
Frick
®
Address
AB
Address
Modbus
Address
Description of Data
Value Codes
4182
N41:82
44183 Digital Out 1 Control Action
4183
N41:83
44184 Digital Out 2 Control Action
4184
N41:84
44185 Digital Out 3 Control Action
4185
N41:85
44186 Digital Out 4 Control Action
4186
N41:86
44187 Digital Out 5 Control Action
4187
N41:87
44188 Digital Out 6 Control Action
4188
N41:88
44189 Digital Out 7 Control Action
4189
N41:89
44190 Digital Out 8 Control Action
4190
N41:90
44191 Digital Out 9 Control Action
4191
N41:91
44192 Digital Out 10 Control Action
0 = Greater Than
1 = Less Than
4200 N42:00 44201
Cooling
Configuration
0 = Disabled
1 = Single Stage
2 = Two Stage
3 = Three Stage
4 = Four Stage
5 = Single Modulated Value
6 = Flooded Single Stage
7 = Flooded Two Stage
8 = Two Position Valve with Modulated Output
4201 N42:01 44202
Supply
Burner Configuration
0 = Disabled
1 = Direct
2 = Indirect
4202 N4202 44203
Heating
Configuration
0 = Disabled
1 = Single Stage
2 = Single Modulated Valve
3 = Two Position Valve with Modulated Output
4203 N42:03 44204
Dehumidification
Configuration
0 = Disabled
1 = Cooling
2 = Desiccant
3 = Desiccant and Cooling
4204
N42:04
44205 Supply Fan Configuration
0 = Constant Air Volume
4205 N42:05 44206
Exhaust
Configuration
0 = Disabled
1 = Single Stage
2 = Two Stage
4206 N42:06 44207
Temperature Configuration
0 = Room Air Control
1 = Return Air Control
2 = Discharge Air Control
4207 N42:07 44208
Damper
Configuration
0 = Mixed Air With Dry Bulb & Cleanup
1 = 100% Outside Air
4208
N42:08
44209 Room Pressure Configuration
0 = Disabled
1 = Room Pressure High Limit
4209 N42:09 44210
Defrost
Configuration
0 = Disabled
1 = Standard Defrost
2 = Sequential Defrost
4210 N42:10 44211
Mode
Configuration
0 = Single Process
1 = Single Process and Cleanup
2 = Dual Process
3 = Dual Process and Cleanup
4211 N42:11 44212
Suction
Configuration
0 = Cooling Always
1 = Cooling with Liquid
2 = Flooded
4212
N42:12
44213 Cooling Active Configuration
4213
N42:13
44214 Supply Burner Active Configuration
4214 N42:14 44215
Heating
Active
Configuration
0 = Process
1 = Cleanup
2 = Process and Cleanup