INSTALLATION AND SETUP
Electrical Installation
20
Maximum Motor Cable Length
1
Based on a 5% voltage drop with 1000 ft limit.
Notes:
•
Drive input voltage and motor nameplate voltage must match.
•
The use of 600 V minimum rated motor cable is required.
•
Maximum allowable wire lengths are measured between the controller and motor, based on
AIM Manual requirements with 1000 ft limit. Larger wire and filtering are required if exceeding
the 1000 ft limit.
•
Flat-jacketed submersible motor cable is recommended. All splices in the motor cable must be
properly sealed with watertight shrink tubing. Use extreme caution to avoid damaging or
compromising the motor cable insulation during installation or service.
Conduit Locations and Sizing
Use appropriate strain relief or conduit connectors.
1.
Incoming power supply—Hole = 0.88 in. (22.2 mm)
2. Power output to motor—Hole = 0.88 in (22.2 mm), Knockout = 1.11 in. (28.2 mm)
3. Control wiring (transducer/sensor) input—Hole = 0.5 in. (12.7 mm)
Model
Motor Family
Motor
Voltage
Horsepower
AWG 600V Copper Wire Sizes, 75° C Insulation, and Motor Cable
Lengths (in feet)
1
14
12
10
8
6
4
SubDrive
Utility
244 502 xxxx
115
1/3 (0.25 kW)
100
160
250
390
620
960
244 504 xxxx
115
1/2 (0.37 kW)
100
160
250
390
620
960
244 505 xxxx
230
1/2 (0.37 kW)
400
650
1000
–
–
–
244 507 xxxx
230
3/4 (0.55 kW)
300
480
760
1000
–
–
244 508 xxxx
230
1.0 (0.75 kW)
250
400
630
990
–
–
244 509 xxxx
230
1.5 (1.1 kW)
190
310
480
770
1000
–