27
The P36D-1 is approved for a 40 ft. straight vertical,
with
rigid pipe
vent systems for Propane and Natural
Gas, as per the diagram 1.
The shaded area in the diagram 1 shows all
allowable combinations of straight vertical and
offset to vertical terminations with
rigid pipe
vent
systems for Propane and Natural Gas. Maximum
two 45
o
elbows allowed.
• Vent must be supported at offsets
• Firestops are required at each fl oor level
and whenever passing through a wall.
• Maintain clearances to combustibles.
Diagram 1
INSTALLATION