background image

5. Storage and maintenance

 

5-1. Storage

Charge the UPS for at least 7 hours before storing the unit. Cover the UPS, and place it upright in a cool, dry location. During 

storage, recharge the battery in accordance with the following table:

5-2. Maintenance

The UPS system operates with hazardous voltages. Repairs may be carried out only by qualified maintenance personnel.

Even after the unit is disconnected from the mains, components inside the UPS system are still connected to the battery 

packs which are potentially dangerous.

Before carrying out any kind of service and/or maintenance, disconnect the batteries and verify that no current is present and 

no hazardous voltage exists in the terminals of high capability capacitor such as BUS-capacitors.

Servicing of batteries should be performed or supervised by personnel with knowledge of batteries and the required

precautions. Keep unauthorized personnel away from batteries.    

Verify that no voltage between the battery terminals and the ground is present before maintenance or repair. In this product, 

the battery circuit is not isolated from the input voltage. Hazardous voltages may occur between the battery terminals and the 

ground.

A battery can present a risk of electric shock and high short circuit current. The following precaution should be observed 

when working on batteries:

• Remove watches, rings or other metal objects.

• Use tools with insulated handles.

Replace batteries with the same type and number of units.

Do not attempt to dispose of batteries by burning them. This could cause battery explosion. The batteries must be properly 

deposed according to local regulation.

Do not open or destroy batteries. Released electrolyte is highly poisonous and harmful to the skin and eyes.

Replace the fuse only with the same type and amperage in order to avoid fire hazards.

Do not disassemble the UPS system.

4. Troubleshooting guide

If the UPS system does not operate correctly, use the table below to troubleshoot the problem.

-25°C - 40°C
40°C - 45°C

Every 3 months
Every 2 months

1-2 hours
1-2 hours

Storage temperature Recharge frequency

Runtime

Even though the mains supply is normal, 
and there are no status indicators or 
alarms. 
The       icon and the warning code      blink 
on the LCD display and the alarm starts 
beeping once every second.
The       and           icons blink on the LCD 
display and the alarm starts beeping once 
every second.

The        and            icons blink on the LCD 
display and the alarm beeps twice every 
second.

Fault code 43 becomes illuminated along 
with the            icon on the LCD display, 
and the alarm starts beeping continuously.
Fault code 14 becomes illuminated along 
with the             icon on the LCD display, 
and the alarm starts beeping  continuously.  
Fault codes 01, 02, 03, 04, 11, 12, 13, 
14,1A, 21, 24, 35, 36, 41, 42 or 43 become 
illuminated on the LCD display, and the 
alarm starts beeping continuously. 
 

Battery backup time is shorter than its 
nominal value.

The       and     icons become illuminated 
on the LCD display, and the alarm starts 
beeping once every second.

The AC input power is not properly 
connected.

EPO function is enabled.

The external or internal battery is 
incorrectly connected.

UPS is overloaded.
 
UPS is overloaded. Devices connected to 
the UPS are fed directly by the electrical 
network via the bypass.
After repetitive overloads, the UPS is 
locked in the Bypass mode. Connected 
devices are fed directly by the mains.

The UPS shuts down automatically upon 
detecting an overload on the UPS output.

The UPS shuts down automatically upon 
detecting a short circuit on the UPS 
output.
A UPS internal fault has occurred. There 
are two possible causes:
1. Power is continued to be supplied to 
the load, but is done directly from the AC 
grid via a bypass.
2. Power is no longer supplied to the load. 

Batteries are not fully charged.

Defective batteries.  
Fan is either locked, has stopped 
working, or the UPS temperature is too 
high.

Check to make sure the power cord is 
firmly connected to an AC wall socket. 

Set the circuit in closed position to 
disable EPO function.

Check if all batteries are properly
connected.

Remove excess loads from the UPS 
output.
Remove excess loads from the UPS 
output.

Remove excess loads from UPS output 
first. Then shut down the UPS and restart 
it.

Remove excess loads from the UPS 
output and restart the unit once again.

Check the output wiring and if the 
connected devices are short-circuited.

Please contact the dealer or service 
center.

Charge the batteries for at least 7 hours 
and then check their capacity. If the 
problem still persists, consult your dealer. 
Contact your dealer for a replacement.

Check fans and notify dealer.

Symptom

Possible cause

Solution

Summary of Contents for FDC-106K

Page 1: ...2 y e a r W a r r a n t y User Manual Uninterruptible Power Supply System FDC 106K FDC 110K...

Page 2: ...3 Initial setup Do not connect appliances or equipment that may overload the UPS system such as big motor type equipment to the UPS output sockets or terminal Place cables in such a way that no one c...

Page 3: ...he carrier or dealer where you purchased the unit Safety IEC EN 62040 1 EMI Conducted emission Radiated emission EMS ESD RS EFT SURGE CS Power frequency magnetic field Low frequency signals Warning Th...

Page 4: ...input and output wires and the input and output terminals are connected tightly Note 2 There are two output terminal configurations to meet customers diverse requirements for serial or parallel connec...

Page 5: ...with a technician to ensure that the load current will not exceed this limitation Note 2 When connecting to low voltage and high voltage at the same time as described in option 4 the L1 N1 and L2 N2...

Page 6: ...for calculating the capacity of the UPS as energy consumption increases during initial power on Description UPS status Bypass mode Battery mode Fault mode Warning Overload Others Fault All Buzzer stat...

Page 7: ...inverter has been turned off Note 2 After turning off the UPS please beware that the UPS is operating in Bypass mode and there is a risk of power loss for connected devices 2 In Bypass mode output vol...

Page 8: ...it will cause permanent damage to the equipment 5 Connect both parallel cables between each UPS the communications cable DB 25 and the load balancing cable as illustrated below Once the above connect...

Page 9: ...ing Parameter 2 Output frequency To set the output frequency choose any of the following three options in parameter 2 50 0Hz The output frequency is set to 50 0Hz 60 0Hz The output frequency is set to...

Page 10: ...0 of the nominal voltage Interface Setting 06 Voltage range for ECO mode Parameter 2 Sets low frequency point for ECO mode 50Hz system Ranges from 46 0Hz to 48 0Hz 60Hz system Ranges from 56 0Hz to 58...

Page 11: ...tery specifications Interface Setting 14 Charger voltage adjustment 15 Output voltage adjustment Parameter 2 You may choose Add or Sub to adjust the output voltage Parameter 3 The voltage ranges from...

Page 12: ...e switch is open Bypass is unstable Boot loader is missing Warning event Battery is not connected Over charge Low battery Overload Fan failure EPO enable Over temperature Charger failure Locked in byp...

Page 13: ...rning code blink on the LCD display and the alarm starts beeping once every second The and icons blink on the LCD display and the alarm starts beeping once every second The and icons blink on the LCD...

Page 14: ...Environment Operating temperature Storage temperature Relative humidity Operating altitude Audible noise Physical appearance Product Dimensions Product Weight Additional information Warranty 6000VA 6...

Page 15: ...www forzaups com...

Reviews: