
Function
Button
ON/Enter
Button
OFF/ESC
Button
Test/Up
Button
Mute/Down
Button
Test/Up +
Mute/Down
Button
Turns on the UPS
: Press and hold this button over 0.5 second to turn on the UPS.
Enter Key
: Press this button to confirm the selected settings of the configuration menu.
Turns off the UPS
: Press and hold this button for 0.5 second to turn off the UPS.
Esc key
: Press this button to return to the last setting of the configuration menu.
Battery test
: Press and hold this button for 0.5 second to test the battery status while
in AC mode, or CVCF mode.
UP key
: Press this button to display the next selection in the configuration menu.
Mutes the alarm:
Press and hold the button for 0.5 second to mute the buzzer.
Please refer to sections below for details.
Down key
: Press this button to display previous selection in the configuration menu.
Press and hold these two buttons simultaneously for 1 second either to enter
or exit the menu settings.
•
•
•
•
•
•
•
•
•
3. Advanced operation
3-1. Description of buttons and functions
3-2. LED Indicators and LCD panel
There are 4 LEDs on front panel to show the UPS working status:
* CVCF stands for converter mode
Mode
LED
UPS startup
No Output
Bypass mode
AC mode
Battery mode
CVCF mode
Battery Test
ECO mode
Fault
Bypass
Line
Battery
Fault
BYPASS
LINE
BATTERY
FAULT
LED indicators
Note: means LED is illuminated means LED is not illuminated
Option 3:
After connecting N1 and L2, it becomes one high-voltage output (208/220/230/240V) at L1-N2 for 100% of the UPS rated current.
Connect load to L1-N2.
Option 4:
After connecting N1 and L2, it becomes three outputs, one high-voltage output (208/220/230/240V) at L1-N2 and two low-voltage
outputs (104/110/115/120V) at L1-N1 and L2-N2. However, there is a limit for current rating at L1-N1 and L2-N2: 25A for 6K model
and 42A at 10K model. You must connect the load taking into account such limits. Please read the notes before installation.
Connect the low-voltage load to L1-N1 and L2-N2, and connect the high-voltage load to L1-N2.
Note 1: If any load current in L1-N1 or L2-N2 is higher than 25A in 6K model and 42A in 10K model, the UPS will still operate
normally without overload warning because the total load is under the specified limit. However, the high current can damage the
isolation transformer due to overheat caused by the high current. Hence, the installation must be done with a technician to ensure
that the load current will not exceed this limitation.
Note 2: When connecting to low-voltage and high-voltage at the same time as described in option 4, the L1-N1 and L2-N2 will feed
low-voltage loads in non-isolated status because high-voltage is being generated by shorting N1-L2. If keeping a connected load in
isolated status is required, we recommend that you may only use two low-voltages at L1-N1 or L2-N2 like illustrated in option 1, and
also make sure that the total current in L1-N1 or L2-N2 does not exceed the value specified in Note1.
2-5. ForzaTracker monitoring software
ForzaTracker is a new generation of UPS monitoring software, which provides user-friendly interface to monitor and control your
Uninterruptible Power System. This unique software provides safe auto-shutdown for multi-computer systems during power failures.
With this software, users can monitor and control any UPS on the same LAN no matter how far they might be from the UPS.
Installation procedure for Windows users:
1. Use the supplied CD or go to the website:
http://www.forzaups.com/us/driver-downloads/
.
2. After clicking the software icon, choose the required operation system.
3. Follow the on-screen instructions to install the software.
4. When you finished downloading all required files, enter the serial No (Installation Password): 5242-87f6-64re-di8d-986u to install
the software (include the hyphens).
To load
L 1 N1 L 2 N2 L N
To load 1
To load 2
To load 3
L 1 N1 L 2 N2 L N
5. In order to access as Administrator, input the password: 111296.
6. When your computer restarts, the management software will appear as a light blue round icon located in the system tray, near
the clock.
For Mac users, please refer to the ForzaTracker quick installation guide inside the Mac folder.
Display
Function
Backup time information
Fault information
Mute operation
Output and battery voltage information
Load information
Mode operation information
Provides a digital indication of the battery discharge time.
H: hours M: minutes S: seconds
Indicates that a warning or fault has occurred.
Displays the fault codes, listed in detail in the sections below
Indicates that the UPS alarm has been disabled.
Provides an indication of the output voltage, frequency or battery
voltage.
VAC: output voltage VDC: battery voltage Hz: frequency
Indicates the load level at 0-25%, 26-50%, 51-75%, and 76-100%
Indicates the load or the output is short-circuited.
Overload indication.
Indicates that the UPS is connected to the mains.
Indicates the battery is in working status.