Forza FDC-106K User Manual Download Page 9

1. Failure to connect the Non-isolated neutral between each UPS may permanently damage the units.

2. Connect the output of each UPS to an output breaker.

3. Connect all output breakers to a main breaker. The latter is the one that will be connected to the loads.

4. If using external power banks, each UPS must be connected to its own power bank. In the event a single power bank is used  

    for all the UPS units, it will cause permanent damage to the equipment.

5. Connect both parallel cables between each UPS, the communications cable (DB-25) and the load balancing cable, as  

   

    illustrated below:

Once the above connections are completed, verfify that the following conditions are met:

1. Verify that the input voltage is the same for all UPS units (208, 220, 230 o 240V)

2. Turn on the UPS and the battery breaker located on the back panel of the UPS.

3. If the configuration is successful, the following screen will be displayed in all UPS units.

4. Verify the output voltage in Bypass mode using one enabled output breaker.

5. Next, turn the other output breaker on making sure that output is the same ouput in every UPS. The output difference among  

    all UPS units must not exceed 1V.

6. Once you have checked all the above, turn OFF all the UPS units and output breakers in order for this configuration to take     

    effect. 

7. Finally, power on the UPS units to begin operation in Parallel mode.

3-6. Abbreviations on the LCD display

3-7. UPS parameter settings

Three parameters need to be configured in order to set up the UPS. Refer to the following diagram.

List of the 15 programs for parameter 1:

*Y means that this program can be set in this mode

09
10
11
12
13
14
15

Y

Y
Y
Y
Y

Y

Y
Y
Y

Y

Y
Y
Y

Y

Y
Y
Y
Y

Y

Y
Y
Y
Y

Reserved for future use
Reserved for future use

01
02
03
04
05
06
07
08

Y
Y
Y
Y
Y
Y
Y
Y
Y

Y
Y
Y

Output voltage
Output frequency
Voltage range for bypass
Frequency range for bypass
ECO mode enable/disable
Voltage range for ECO mode
ECO mode frequency range setting
Bypass mode setting
Battery backup time setting
Reserved  
Reserved  
Hot standby function enable/disable
Battery voltage adjustment
Charger voltage adjustment
Output voltage adjustment

Code

Description

Bypass

Y

AC

ECO CVCF Battery Battery

test

Abbreviation

Display content

Meaning

ADD
ON
OFF
FBD
OPN
RES
PAR

Add
On
Off
Not allowed
Allow
Reserved
Parallel

Note: All parameter settings will be saved only when UPS shuts down normally with internal or external battery connection. (Normal 

UPS shutdown means turning off input breaker in bypass/no output mode).

Parameter 3: Output voltage

You may choose the following output voltage in parameter 3:

For 100/110/115/120/127VAC models, you may choose the following output 

voltage:

208: The output voltage is 208VAC

220: The output voltage is 220VAC

230: The output voltage is 230VAC

240: The output voltage is 240VAC

100: The output voltage is 100VAC

110: The output voltage is 110VAC 

115: The output voltage is 115VAC 

120: The output voltage is 120VAC

127: The output voltage is 127VAC

Interface

Setting

Parameter 2: Output frequency

To set the output frequency, choose any of the following three options in 

parameter 2:

50.0Hz: The output frequency is set to 50.0Hz.

60.0Hz: The output frequency is set to 60.0Hz.

ATO: When selected, the output frequency will be set according to the latest 

normal utility frequency. If it ranges from 46Hz to 54Hz, the output frequency 

will be 50.0Hz.

If it ranges from 56Hz to 64Hz, the output frequency will be set at 60.0Hz. 

ATO is the default setting.

Parameter 3: Frequency mode

Enables you to set the output frequency in either CVCF mode or no CVCF 

mode. You may choose any of the following two options in parameter 3:

CF: Sets the UPS in the CVCF mode. If selected, the output frequency will be 

fixed at 50Hz or 60Hz according to the setting in parameter 2. The input 

frequency could range from 46Hz to 64Hz.

NCF: Sets the UPS to normal mode (not CVCF mode).

If selected, the output frequency will synchronize with the input frequency 

within 46~54 Hz at 50Hz or within 56~64 Hz at 60Hz according to the setting 

defined in parameter 2.

If 50Hz is selected in parameter 2, the UPS will transfer to battery mode 

provided the input frequency does not fall within 46~54Hz range. If 60Hz is 

selected in parameter 2, the UPS will transfer to battery mode provided the 

input frequency does not fall within the 56~64Hz range.

*If ATO is selected in Parameter 2, Parameter 3 will show the current

frequency

Interface

Setting

02: Output frequency settings

01: Output voltage settings

60 Hz, CVCF mode

50 Hz, Normal mode

ATO

Note: If the UPS is set to CVCF mode, the bypass function will be disabled automatically.

But when a single UPS without parallel function is powered on with utility power and before the UPS finishes the startup, there will 

be a few seconds of voltage pulse (same as the input voltage) on the bypass output.

If you need to remove the pulse on this mode to better protect your load, you could contact the dealer for help.

This situation will not happen in UPS units working on parallel mode.

 

 

Parameter 1

 

Parameter 2

 

Parameter 3

 

Parameter 1: it is used for the different configuration options. There are 15 

programs to set up. Refer to the table below.

Parameter 2 and parameter 3: they represent the setting options or values of 

each program.

Summary of Contents for FDC-106K

Page 1: ...2 y e a r W a r r a n t y User Manual Uninterruptible Power Supply System FDC 106K FDC 110K...

Page 2: ...3 Initial setup Do not connect appliances or equipment that may overload the UPS system such as big motor type equipment to the UPS output sockets or terminal Place cables in such a way that no one c...

Page 3: ...he carrier or dealer where you purchased the unit Safety IEC EN 62040 1 EMI Conducted emission Radiated emission EMS ESD RS EFT SURGE CS Power frequency magnetic field Low frequency signals Warning Th...

Page 4: ...input and output wires and the input and output terminals are connected tightly Note 2 There are two output terminal configurations to meet customers diverse requirements for serial or parallel connec...

Page 5: ...with a technician to ensure that the load current will not exceed this limitation Note 2 When connecting to low voltage and high voltage at the same time as described in option 4 the L1 N1 and L2 N2...

Page 6: ...for calculating the capacity of the UPS as energy consumption increases during initial power on Description UPS status Bypass mode Battery mode Fault mode Warning Overload Others Fault All Buzzer stat...

Page 7: ...inverter has been turned off Note 2 After turning off the UPS please beware that the UPS is operating in Bypass mode and there is a risk of power loss for connected devices 2 In Bypass mode output vol...

Page 8: ...it will cause permanent damage to the equipment 5 Connect both parallel cables between each UPS the communications cable DB 25 and the load balancing cable as illustrated below Once the above connect...

Page 9: ...ing Parameter 2 Output frequency To set the output frequency choose any of the following three options in parameter 2 50 0Hz The output frequency is set to 50 0Hz 60 0Hz The output frequency is set to...

Page 10: ...0 of the nominal voltage Interface Setting 06 Voltage range for ECO mode Parameter 2 Sets low frequency point for ECO mode 50Hz system Ranges from 46 0Hz to 48 0Hz 60Hz system Ranges from 56 0Hz to 58...

Page 11: ...tery specifications Interface Setting 14 Charger voltage adjustment 15 Output voltage adjustment Parameter 2 You may choose Add or Sub to adjust the output voltage Parameter 3 The voltage ranges from...

Page 12: ...e switch is open Bypass is unstable Boot loader is missing Warning event Battery is not connected Over charge Low battery Overload Fan failure EPO enable Over temperature Charger failure Locked in byp...

Page 13: ...rning code blink on the LCD display and the alarm starts beeping once every second The and icons blink on the LCD display and the alarm starts beeping once every second The and icons blink on the LCD...

Page 14: ...Environment Operating temperature Storage temperature Relative humidity Operating altitude Audible noise Physical appearance Product Dimensions Product Weight Additional information Warranty 6000VA 6...

Page 15: ...www forzaups com...

Reviews: