Forza FDC-106K User Manual Download Page 4

1.   RS-232 communication port

2.   USB communication port

3.   Emergency power off (EPO) connector

4.   Parallel current port

5.   Parallel data ports 

6.   Intelligent slot

7.   Charger fan

8.   Power stage fan

9.   Maintenance bypass switch

10. Input circuit breaker

11. Isolation transformer fan

12. Input/output terminal (Refer to diagram 2 for details)

13. Output terminal 1

14. Output terminal 2

15. External battery connector 

16. Utility input terminal

17. Non-isolated neutral terminal

2-3. Single UPS installation

 

Installation and wiring must be performed by qualified personnel, and in accordance with the local electrical regulations and codes. 

Also, you must observe the following instructions:

1) Make  sure  the  mains  wire  and  breakers in the building are enough for the rated capacity of  the UPS  to avoid the hazards     

    of electric shock or fire.

    Note: Do not use a wall receptacle as the input power source for the UPS, as its rated current is less than the UPS maximum  

    input current. Failure to do so may result in a broken or burned out receptacle.

2) For safety considerations, turn off the mains switch in the building before installation.

3) Turn  off  all  the  devices  before  connecting  them  to  the  UPS.

4) Wiring sizes should be installed in accordance with the following table:

Note 1: The  cable  for 6K should be able to withstand currents of over 40A. It is recommended to use a 10AWG or thicker wire 

for safety and efficiency.

Note 2: The cable for 10K should be able to withstand currents of over 63A. It is recommended to use an 8AWG or thicker wire 

for safety and efficiency.

Note 3: For single model, it is not necessary to connect the non-isolated neutral terminal.

Note 4: The color selection of wires should be made according to the local electrical codes and regulations.

5) Remove the terminal block cover on the rear panel of UPS. Proceed to connect the wires according to the following terminal       

    block diagrams: (Make sure to attach the earth wire first when connecting the wires. When removing the wiring, make sure to  

    remove the earth wire last).

Note 1: Make sure that the input and output wires and the input and output terminals are connected tightly.

Note 2: There are two output terminal configurations to meet customers’ diverse requirements for serial or parallel connection. 

Please refer to section 2.4.

Note 3: Install the leak current protective breaker at the output power distribution panel of the UPS, if necessary.

6) Put the terminal block cover back in the rear panel of the UPS.

         Warning:

• For safety considerations, switch all power off using the main switch before installation.

Note: The battery breaker must also be set to OFF before installing the battery pack.

• Pay close attention to the rated battery voltage marked on the rear panel. If you want to change the number of batteries, please       

   make sure you modify the settings accordingly. A connection with the wrong battery voltage may cause permanent damage to the  

   UPS. Make sure the voltage of the battery pack is correct.

• Pay close attention to the polarity markings on the external battery terminal block, and make sure to match the correct battery       

   polarity of the cells. Wrong connection may cause permanent damage to the UPS.

• Make sure the protective earth ground wiring is correctly installed. The wire current specification, color, position, connection and       

   conductance reliability should be checked carefully.

• Make sure the utility input and output wiring is correct. The wire current specification, color, position, connection and conductance    

   reliability should be checked carefully. Make sure the L/N wiring is correct, not reverse and short-circuited.

2-4. Output configuration

Option 1:

There are 2 sets of low-voltage outputs (104/110/115/120V) on L1-N1 and L2-N2. Each set is able to provide 50% of the UPS rated 

current. Connect one load to L1-N1 and the other load to L2-N2.

Option 2:

After connecting L1-L2 and N1-N2, it becomes one low-voltage output (104/110/115/120V) at L1-N1 for 100% of the UPS rated  

current.  Connect  load  to  L1-N1 or  L2-N2.

Wiring specification (AWG)

Model

Input

Ground

Output

Non-isolated

Neutral

6K

10K

10

8

10

8

10

8

10

8

Terminal block wiring diagram of 6K/10K

To load 1

To load 2

L 1     N1      L 2     N2       L      N

To load 

L 1     N1      L 2     N2       L      N

Input neutral 

Input line

Output 2 neutral

Output 2 line

Non-isolated neutral 

Output 1 line 

Output 1 neutral/ground

Summary of Contents for FDC-106K

Page 1: ...2 y e a r W a r r a n t y User Manual Uninterruptible Power Supply System FDC 106K FDC 110K...

Page 2: ...3 Initial setup Do not connect appliances or equipment that may overload the UPS system such as big motor type equipment to the UPS output sockets or terminal Place cables in such a way that no one c...

Page 3: ...he carrier or dealer where you purchased the unit Safety IEC EN 62040 1 EMI Conducted emission Radiated emission EMS ESD RS EFT SURGE CS Power frequency magnetic field Low frequency signals Warning Th...

Page 4: ...input and output wires and the input and output terminals are connected tightly Note 2 There are two output terminal configurations to meet customers diverse requirements for serial or parallel connec...

Page 5: ...with a technician to ensure that the load current will not exceed this limitation Note 2 When connecting to low voltage and high voltage at the same time as described in option 4 the L1 N1 and L2 N2...

Page 6: ...for calculating the capacity of the UPS as energy consumption increases during initial power on Description UPS status Bypass mode Battery mode Fault mode Warning Overload Others Fault All Buzzer stat...

Page 7: ...inverter has been turned off Note 2 After turning off the UPS please beware that the UPS is operating in Bypass mode and there is a risk of power loss for connected devices 2 In Bypass mode output vol...

Page 8: ...it will cause permanent damage to the equipment 5 Connect both parallel cables between each UPS the communications cable DB 25 and the load balancing cable as illustrated below Once the above connect...

Page 9: ...ing Parameter 2 Output frequency To set the output frequency choose any of the following three options in parameter 2 50 0Hz The output frequency is set to 50 0Hz 60 0Hz The output frequency is set to...

Page 10: ...0 of the nominal voltage Interface Setting 06 Voltage range for ECO mode Parameter 2 Sets low frequency point for ECO mode 50Hz system Ranges from 46 0Hz to 48 0Hz 60Hz system Ranges from 56 0Hz to 58...

Page 11: ...tery specifications Interface Setting 14 Charger voltage adjustment 15 Output voltage adjustment Parameter 2 You may choose Add or Sub to adjust the output voltage Parameter 3 The voltage ranges from...

Page 12: ...e switch is open Bypass is unstable Boot loader is missing Warning event Battery is not connected Over charge Low battery Overload Fan failure EPO enable Over temperature Charger failure Locked in byp...

Page 13: ...rning code blink on the LCD display and the alarm starts beeping once every second The and icons blink on the LCD display and the alarm starts beeping once every second The and icons blink on the LCD...

Page 14: ...Environment Operating temperature Storage temperature Relative humidity Operating altitude Audible noise Physical appearance Product Dimensions Product Weight Additional information Warranty 6000VA 6...

Page 15: ...www forzaups com...

Reviews: