Forza FDC-106K User Manual Download Page 11

Parameter 2: 

HS.H: Enables or disables the Hot standby function. You may choose one of 

the following two options in Parameter 3:

YES: Hot standby function is enabled. It means that the current UPS is set to 

hot standby, and it will restart once electricity is reestablished, even without 

having a battery connected.

NO: Hot standby function is disabled.

The UPS is operating in normal mode and cannot restart without battery.

Interface

Setting

12: Hot standby function enable/disable

Parameter 2:

Select Add or Sub function to adjust battery voltage to its actual reading.

Parameter 3: the voltage ranges from 0V to 5.7V, the default value is 0V.

Interface

Setting

13: Battery voltage adjustment

Parameter 2: You may choose Add or Sub to adjust the charger voltage

Parameter 3: The voltage ranges from 0V to 9.9V, the default value is 0V.

NOTE:

*Before making any voltage adjustment, be sure to disconnect all batteries 

first to get the accurate charger voltage.

*We strongly suggest using the default value (0). Any modification should 

match battery specifications.

Interface

Setting

14: Charger voltage adjustment

15: Output voltage adjustment

Parameter 2: You may choose Add or Sub to adjust the output voltage.

Parameter 3: The voltage ranges from 0V to 6.4V, the default value is 0V.

Interface

Setting

3-8. Operating mode/Status description

When parallel UPS systems are successfully set up, an additional screen with “PAR” in parameter 2 will be displayed and assigned 

a number in parameter 3, as shown below. The master UPS will be assigned “001” as default, while the slave UPSs will be identified 

as either “002” or “003”. The assigned numbers may be changed dynamically during operation.

Description

LCD display

AC mode

ECO mode

Description

LCD display

CVCF  mode

Description

LCD display

Operating mode/status

When the input voltage is within an acceptable range, the UPS will provide pure and 

stable AC power to the output. The UPS will also charge the battery in AC mode.

When the input voltage is within the voltage regulation range and ECO 

mode is enabled, the UPS will bypass voltage to output for energy saving.

When input frequency is within 46 and 64Hz, the UPS can be set at a constant output 

frequency of 50Hz or 60Hz. The UPS will still charge the battery under this mode.

Summary of Contents for FDC-106K

Page 1: ...2 y e a r W a r r a n t y User Manual Uninterruptible Power Supply System FDC 106K FDC 110K...

Page 2: ...3 Initial setup Do not connect appliances or equipment that may overload the UPS system such as big motor type equipment to the UPS output sockets or terminal Place cables in such a way that no one c...

Page 3: ...he carrier or dealer where you purchased the unit Safety IEC EN 62040 1 EMI Conducted emission Radiated emission EMS ESD RS EFT SURGE CS Power frequency magnetic field Low frequency signals Warning Th...

Page 4: ...input and output wires and the input and output terminals are connected tightly Note 2 There are two output terminal configurations to meet customers diverse requirements for serial or parallel connec...

Page 5: ...with a technician to ensure that the load current will not exceed this limitation Note 2 When connecting to low voltage and high voltage at the same time as described in option 4 the L1 N1 and L2 N2...

Page 6: ...for calculating the capacity of the UPS as energy consumption increases during initial power on Description UPS status Bypass mode Battery mode Fault mode Warning Overload Others Fault All Buzzer stat...

Page 7: ...inverter has been turned off Note 2 After turning off the UPS please beware that the UPS is operating in Bypass mode and there is a risk of power loss for connected devices 2 In Bypass mode output vol...

Page 8: ...it will cause permanent damage to the equipment 5 Connect both parallel cables between each UPS the communications cable DB 25 and the load balancing cable as illustrated below Once the above connect...

Page 9: ...ing Parameter 2 Output frequency To set the output frequency choose any of the following three options in parameter 2 50 0Hz The output frequency is set to 50 0Hz 60 0Hz The output frequency is set to...

Page 10: ...0 of the nominal voltage Interface Setting 06 Voltage range for ECO mode Parameter 2 Sets low frequency point for ECO mode 50Hz system Ranges from 46 0Hz to 48 0Hz 60Hz system Ranges from 56 0Hz to 58...

Page 11: ...tery specifications Interface Setting 14 Charger voltage adjustment 15 Output voltage adjustment Parameter 2 You may choose Add or Sub to adjust the output voltage Parameter 3 The voltage ranges from...

Page 12: ...e switch is open Bypass is unstable Boot loader is missing Warning event Battery is not connected Over charge Low battery Overload Fan failure EPO enable Over temperature Charger failure Locked in byp...

Page 13: ...rning code blink on the LCD display and the alarm starts beeping once every second The and icons blink on the LCD display and the alarm starts beeping once every second The and icons blink on the LCD...

Page 14: ...Environment Operating temperature Storage temperature Relative humidity Operating altitude Audible noise Physical appearance Product Dimensions Product Weight Additional information Warranty 6000VA 6...

Page 15: ...www forzaups com...

Reviews: