Forza FDC-106K User Manual Download Page 12

Battery mode

Description

LCD display

Bypass mode

Battery test

Fault status

Description

LCD display

LCD display

LCD display

Operating mode/status

When the input voltage exceeds the acceptable range or during a power failure, the 

UPS will start supplying power from the battery while the alarm will beep every 4 

seconds.

When input voltage is within the acceptable range and bypass is enabled, turn off the 

UPS in order to transfer the unit to Bypass mode. The alarm beeps every two minutes 

in this case. 

Description

When UPS is in AC mode or CVCF mode, press and hold the Test key for 0.5 second. 

The UPS will beep once and start performing the “Battery test”. The line between I/P 

and inverter icons blinks while the diagnostics is in progress. This operation is used to 

check the battery status.

Description

In the event of abnormal operation, the LCD panel will display the corresponding fault 

message on the LCD panel.

3-9. Fault codes

3-10. Warning indicators

3-11. Warning codes

 

Warning code

01
07
08
09

0A
0B
0D
0E

Warning code

10
21
22
33

3A
3D
3E

Warning event
L1 IP fuse is blown
Line issues are different in a parallel system
Bypass issues are different in parallel system

Cover of maintenance switch is open
Bypass is unstable
Boot loader is missing

Warning event

Battery is not connected

Over charge

Low battery

Overload

Fan failure

EPO enable

Over temperature

Charger failure

Locked in bypass after an overload is 

detected 3 times in 30 minutes

 

 

Fault event
Bus start failure
Bus over
Bus under
Bus unbalance
Inverter soft start failure
High inverter voltage
Low inverter voltage
Inverter output short circuited
Negative power fault
Inverter over current
Inverter waveform abnormal

Fault event
Battery SCR short circuited
Inverter relay short circuited
Charger short circuited
Parallel communication fault
Parallel output current unbalance
Over temperature
CPU communication failure
Overload
Battery turn-on failure
PFC current failure in battery mode
Bus voltage changes too fast

Fault code

01
02
03
04
11
12
13
14
1A
60
63

Fault code

21
24
2a
31
36
41
42
43
6A

6B
6C

Icon

None
None
None
None
None
None
None

 

None
None
None

Icon

None
None  
None
None
None
None
None

 

None
None
None

Warning
Battery low
Overload
Battery unconnected

Over charge

EPO enable
Fan failure/Over temperature
Charger failure
I/P fuse broken
Overload 3 times in 30min

Alarm

Beeps once every second

Beeps twice every second

Beeps once every second

Beeps once every second

Beeps once every second
Beeps once every second
Beeps once every second
Beeps once every second
Beeps once every second

 

 

 

Icon (blinking)

Summary of Contents for FDC-106K

Page 1: ...2 y e a r W a r r a n t y User Manual Uninterruptible Power Supply System FDC 106K FDC 110K...

Page 2: ...3 Initial setup Do not connect appliances or equipment that may overload the UPS system such as big motor type equipment to the UPS output sockets or terminal Place cables in such a way that no one c...

Page 3: ...he carrier or dealer where you purchased the unit Safety IEC EN 62040 1 EMI Conducted emission Radiated emission EMS ESD RS EFT SURGE CS Power frequency magnetic field Low frequency signals Warning Th...

Page 4: ...input and output wires and the input and output terminals are connected tightly Note 2 There are two output terminal configurations to meet customers diverse requirements for serial or parallel connec...

Page 5: ...with a technician to ensure that the load current will not exceed this limitation Note 2 When connecting to low voltage and high voltage at the same time as described in option 4 the L1 N1 and L2 N2...

Page 6: ...for calculating the capacity of the UPS as energy consumption increases during initial power on Description UPS status Bypass mode Battery mode Fault mode Warning Overload Others Fault All Buzzer stat...

Page 7: ...inverter has been turned off Note 2 After turning off the UPS please beware that the UPS is operating in Bypass mode and there is a risk of power loss for connected devices 2 In Bypass mode output vol...

Page 8: ...it will cause permanent damage to the equipment 5 Connect both parallel cables between each UPS the communications cable DB 25 and the load balancing cable as illustrated below Once the above connect...

Page 9: ...ing Parameter 2 Output frequency To set the output frequency choose any of the following three options in parameter 2 50 0Hz The output frequency is set to 50 0Hz 60 0Hz The output frequency is set to...

Page 10: ...0 of the nominal voltage Interface Setting 06 Voltage range for ECO mode Parameter 2 Sets low frequency point for ECO mode 50Hz system Ranges from 46 0Hz to 48 0Hz 60Hz system Ranges from 56 0Hz to 58...

Page 11: ...tery specifications Interface Setting 14 Charger voltage adjustment 15 Output voltage adjustment Parameter 2 You may choose Add or Sub to adjust the output voltage Parameter 3 The voltage ranges from...

Page 12: ...e switch is open Bypass is unstable Boot loader is missing Warning event Battery is not connected Over charge Low battery Overload Fan failure EPO enable Over temperature Charger failure Locked in byp...

Page 13: ...rning code blink on the LCD display and the alarm starts beeping once every second The and icons blink on the LCD display and the alarm starts beeping once every second The and icons blink on the LCD...

Page 14: ...Environment Operating temperature Storage temperature Relative humidity Operating altitude Audible noise Physical appearance Product Dimensions Product Weight Additional information Warranty 6000VA 6...