Forza FDC-106K User Manual Download Page 7

3) If the UPS is overloaded, the  buzzer will beep  twice  every second.

4) In the event of an overload, all unnecessary loads must be removed one by one, to lower the total loads connected to the       

    UPS to less than 80% of its nominal power capacity to prevent  overload  condition.

5) If the overload time exceeds the time specified in AC mode, the UPS will automatically transfer to Bypass mode. After the    

    overload is removed, the UPS will return to AC mode. If the overload time exceeds the time specified in Battery mode, the     

    UPS will transfer to fault status. At this time, if bypass is enabled, the UPS will supply power to the loads using the bypass     

    mode. If the bypass function is disabled or the input power is not within the bypass acceptable range, the output power will     

    be cut off immediately.

4. Charging the batteries

1) Once the UPS is connected to utility power, the unit will charge the batteries automatically, except when the USP is running    

    in Battery mode or while the battery self-test is in progress.

2) It is recommended to charge the batteries at least 10 hours before use to ensure proper backup time.

3) Make sure battery number setting on the control board is consistent with the  actual  connection.

5. Battery mode operation

1) When the UPS is in Battery mode, the buzzer will beep according to the battery capacity.

a. If the battery capacity is more than 25%, the buzzer will beep once every 4 seconds.

b. If the battery voltage drops to the alarm triggering level, the buzzer will beep once every second to indicate that the battery     

    has reached its lowest capacity, and that the UPS will soon shut down automatically. Shutting down non-critical loads at     

    this point will prolong the backup time. If the programmable timer function is enabled, the UPS will shut off programmable    

    output terminals automatically.

Note: There is the risk of data loss or load failure if battery runtime is exceeded.

2) To silence the buzzer sound in Battery mode, press the Mute button.

3) The backup time vary depending upon environment conditions and load types.

4) When the backup time is set at 16.5 hours (LCD panel default value), the UPS will shut down automatically to protect the     

    battery after the discharging period of 16.5 hours is completed. This battery discharge protection can be enabled or disabled  

    using the LCD panel control.

6. Testing the batteries

1) To check the battery status when the UPS is running in AC mode/CVCF mode/ECO mode, press the Test button to initiate      

    the self-diagnostic tool.

2) To maintain the system reliability, the UPS will perform an automatic battery self-test on a periodic basis. The default setting   

    for the battery self-test is once per week.

3) Battery self-test interval can also be set through the monitoring software.

4) When the UPS is in battery self-test mode, the LCD Display and buzzer indication will be the same as in battery mode, with 

the exception that the battery LED will appear blinking in this case.

7. Turn off the UPS with utility power in AC mode

1) Turn off the inverter of the UPS by pressing the OFF button for at least 0.5 second. The buzzer will beep once and the UPS    

    will go into Bypass mode.

    Note 1: If the UPS has been set to enable the bypass output, it will bypass voltage from utility power to the output terminal       

    even though the UPS (inverter) has been turned off.

    Note 2: After turning off the UPS, please beware that the UPS is operating in Bypass mode and there is a risk of power loss      

    for connected devices.

2) In Bypass mode, output voltage of the UPS is still present. In order to shut off the output voltage, switch off the input breaker  

    to the UPS. A few seconds later, there will be no display shown on the LCD panel while the UPS is now completely turned         

    off.

8. Turn off the UPS without utility power supply in Battery mode

1) Turn off the UPS by pressing the OFF button for at least 0.5 second. The buzzer will beep once.

2) The UPS power will shut off output and there will be no indication showing on the display panel.

9. Muting the buzzer

1) To silence the buzzer, press the Mute button for at least 0.5 second. If you press it again, the buzzer will be enabled.

2) Some warning alarms cannot be muted unless the error that triggered them is fixed.

10. Operation in warning status

1) When the Fault LED flashes and the buzzer beeps  once  every  second, it means that the UPS is experiencing operation  

   

    issues. Fault codes are available via the LCD Panel. Refer to the troubleshooting table for additional details.

2) Some warning alarms cannot be muted unless the error that triggered them is fixed.

11. Operation in fault mode

1) When the Fault LED illuminates and the buzzer beeps continuously, it means that there is a fatal error in the UPS. Fault  

   

    Codes are available via the LCD Panel. Refer to the Troubleshooting table for additional details.

2) Check the loads, wiring, ventilation, utility, battery and so on when a fault occurs. Do not try to turn on the UPS again before     

    solving the problems. If the issues persist, contact the dealer or service personnel immediately.

3) In case of emergency, disconnect the UPS from the utility, external battery, and output immediately to avoid danger.

12. Changing battery numbers

1) This operation should only be performed by trained and qualified technicians.

2) Turn off the UPS. If the load cannot be shut down, remove the cover from the maintenance bypass switch on the rear panel      

    of the unit, and slide the maintenance switch to the BPS position.

3) Switch off the input breaker.

4) Remove the UPS cover. Disconnect the battery wire and modify the jumper on the control board to set the battery numbers.  

5) Modify the battery pack to match the setting number in control panel.

6) Then, modify charger voltage according to the table below to match the setting number on the control board. There are 5      

    jumpers on the charger board. Please refer to the below table to modify charger voltage.

7) After executing the previous steps, replace the UPS cover. Switch on the input breaker and the UPS will enter into the  

   

    Bypass mode. If the UPS is in maintenance Bypass mode, turn the maintenance switch to the UPS position before turning      

    on the system.

Note: 0 = no jumper; 1 = connect with jumper; X = the pins are for other functions. 

Note: 0 = no jumper; 1 = connect with jumper.

 

Battery number 

in series

 

JP1

 

pin1 & pin2

 

pin3 & pin4

 

pin5 & pin6

 

pin7 & pin8

 

pin9 & pin10

 

16

 

1

 

0

 

0

 

17

 

0

 

1

 

1

 

18

 

0

 

1

 

0

 

19

 

0

 

0

 

1

 

20

 

0

 

0

 

0

 

 

Battery number 

in series

 

16

 

17

 

18

 

19

 

20

 

Charge 

voltage (V) 

JP01 

JP02 

JP03

 

JP04

 

JP05

 

218  

232  

245  

259  

273  

Input and battery voltage information

Indicates the battery is not connected.

Low battery and low voltage indicator.

Indicates the input voltage or frequency, or battery voltage.

VAC: input voltage  VDC: battery voltage Hz: input frequency

Summary of Contents for FDC-106K

Page 1: ...2 y e a r W a r r a n t y User Manual Uninterruptible Power Supply System FDC 106K FDC 110K...

Page 2: ...3 Initial setup Do not connect appliances or equipment that may overload the UPS system such as big motor type equipment to the UPS output sockets or terminal Place cables in such a way that no one c...

Page 3: ...he carrier or dealer where you purchased the unit Safety IEC EN 62040 1 EMI Conducted emission Radiated emission EMS ESD RS EFT SURGE CS Power frequency magnetic field Low frequency signals Warning Th...

Page 4: ...input and output wires and the input and output terminals are connected tightly Note 2 There are two output terminal configurations to meet customers diverse requirements for serial or parallel connec...

Page 5: ...with a technician to ensure that the load current will not exceed this limitation Note 2 When connecting to low voltage and high voltage at the same time as described in option 4 the L1 N1 and L2 N2...

Page 6: ...for calculating the capacity of the UPS as energy consumption increases during initial power on Description UPS status Bypass mode Battery mode Fault mode Warning Overload Others Fault All Buzzer stat...

Page 7: ...inverter has been turned off Note 2 After turning off the UPS please beware that the UPS is operating in Bypass mode and there is a risk of power loss for connected devices 2 In Bypass mode output vol...

Page 8: ...it will cause permanent damage to the equipment 5 Connect both parallel cables between each UPS the communications cable DB 25 and the load balancing cable as illustrated below Once the above connect...

Page 9: ...ing Parameter 2 Output frequency To set the output frequency choose any of the following three options in parameter 2 50 0Hz The output frequency is set to 50 0Hz 60 0Hz The output frequency is set to...

Page 10: ...0 of the nominal voltage Interface Setting 06 Voltage range for ECO mode Parameter 2 Sets low frequency point for ECO mode 50Hz system Ranges from 46 0Hz to 48 0Hz 60Hz system Ranges from 56 0Hz to 58...

Page 11: ...tery specifications Interface Setting 14 Charger voltage adjustment 15 Output voltage adjustment Parameter 2 You may choose Add or Sub to adjust the output voltage Parameter 3 The voltage ranges from...

Page 12: ...e switch is open Bypass is unstable Boot loader is missing Warning event Battery is not connected Over charge Low battery Overload Fan failure EPO enable Over temperature Charger failure Locked in byp...

Page 13: ...rning code blink on the LCD display and the alarm starts beeping once every second The and icons blink on the LCD display and the alarm starts beeping once every second The and icons blink on the LCD...

Page 14: ...Environment Operating temperature Storage temperature Relative humidity Operating altitude Audible noise Physical appearance Product Dimensions Product Weight Additional information Warranty 6000VA 6...

Page 15: ...www forzaups com...

Reviews: