Summary of Contents for Power Protection Active 1000

Page 1: ...UK ...

Page 2: ...1 Chloride Active UK ...

Page 3: ...1 Chloride Active ENGLISH DEUTSCH ESPAÑOL FRANÇAIS ITALIANO PORTUGUÊS UK DE E FR I P ...

Page 4: ...der der GM Eintragung Lieferung je nach Verfügbarkeit Technische Änderungen vorbehalten Tutti i diritti incluso quelli di traduzione riproduzione di stampa copia concessione di licenze e di utilizzo e simili anche solo di parti del testo sono riservati I trasgressori seranno perseguiti per danni La consegna è soggetta alla disponibilità L azienda si riserva il diritto di variare qualunque informaz...

Page 5: ...3 Chloride Active UK UK DE E FR I P OPERATING MANUAL BEDIENUNGSANLEITUNG MANUAL DE USUARIO MANUAL UTILISATEUR MANUALE D USO MANUAL DE INSTRUÇÕES 4 42 80 118 156 194 ...

Page 6: ...k Mounting the UPS or External Battery Cabinets RT Models Only 3 12 Floor Mounting the UPS or External Battery Cabinets RT Models Only 3 12 1 Mounting the UPS Only 3 12 2 Mounting the UPS plus One External Battery 4 Operation and Commissioning 4 1 Theory of Operation 4 1 1 Line Mode 4 1 2 Battery Mode 4 1 3 Bypass Mode 4 1 4 ECO Mode 4 1 5 Frequency Converter Mode 4 1 6 Other Operating Details 4 1...

Page 7: ...7 UPS Shutdown Procedure 4 4 8 Remote Power Off RPO Remote On Off ROO 5 Communication Interfaces 5 1 Serial Interface 5 2 DB9 Port 5 3 USB Port 5 4 Interface Slot 6 Maintenance 6 1 Cleaning 6 2 UPS Storage 6 3 Battery Testing 6 4 Battery Replacement 6 4 1 Replacing the UPS internal batteries 6 4 2 Battery Disposal 6 5 Front Panel with LCD Display Installation 7 Troubleshooting 8 Technical Speci ca...

Page 8: ...nst jolts and shocks If the UPS is moved from a cold environment to a warmer operating location condensation may occur Before you switch on the unit it must be absolutely dry An acclimatization period of at least two hours is required The UPS must be installed in accordance with the environmental conditions speci ed in sections 3 6 and 3 10 Even with all buttons in OFF position the unit UPS is not...

Page 9: ...l waste For replacement of batteries located in a service access area Servicing of batteries should be performed or supervised by personnel knowledgeable about batteries and the required precautions When replacing batteries replace with the same type and number of batteries or battery packs Do not dispose of batteries in a re The batteries may explode Do not open or mutilate batteries Released ele...

Page 10: ...91 263 EWG 92 31 EWG and 93 68 EWG Conformity is established through compliance with the following standards EN 62040 1 1 EN 62040 2 Additional information regarding adherence to these directives is included in the appendices NSR and EMC of the EU Declaration of Conformity If needed the EU Declaration of Conformity can be requested from the manufacturer 1 7 Repacking of Unit Do not pack the unit u...

Page 11: ...tandard front panels with LCD display are available as accessory These front panels have to be ordered separately Installation of the front panel with LCD display must be carried out by quali ed technicians Please contact the responsible customer service representative For further details on installation please see section 6 5 The following battery packs are available Housing Designation Nominal P...

Page 12: ...ions which if not observed present risk of electric shock may endanger your life your health reliability of your UPS or the security of your data NOTE Indicates instructions and comments that provide further details on the UPS and complement the main text 2 4 Documentation structure These instructions can be supplemented with additional sheets which e g describe speci c extensions or options ...

Page 13: ...whose content is subject to changes according to local markets 3 3 Scope of delivery The following items are included within the packaging 3 3 1 Tower units UPS 1 x this user manual 1 x UPS unit 1 x quickstart guide 1 x CD with user software 2 x connection cables IEC320 C14 male IEC C13 female for the UPS output 1 x RS232 interface cable 1 x USB cable 3 3 2 Tower units Battery Packs 1 x Battery Pa...

Page 14: ...perature and humidity storage limits 3 5 Handling The UPS must be kept upright at all times and handled with care Damage may be caused if dropped or subjected to severe impact 3 6 Environmental Conditions The UPS tower version must be installed vertically The UPS rack tower version RT hereinafter can be installed vertically or horizontally depending on the desired arrangement In any case it must b...

Page 15: ...ccess to the UPS 3 10 Installation Data 3 11 Rack Mounting the UPS or External Battery Cabinets RT Models Only The Rack Tower UPS s and external battery packs can be rack mounted in four post frames The UPS and external battery packs use identical mounting hardware and the procedure for mounting either is the same ATTENTION The UPS draws cooling air from the front If the rack has a door on the fro...

Page 16: ...the UPS into a rack To prepare the UPS and external batteries for use in a rack con guration rst install the sliding rails optional accessory and then install the UPS and batteries following the steps below 1 Attach rear of rails to rear of rack with two screws provided 2 Attach front of rails to front of rack with one screw provided 3 Assemble side rails and secure each rail together with three s...

Page 17: ...ION Use all supplied mounting hardware on each UPS and external battery After mechanical installation is complete please read section 4 for proper commissioning and operation of the system 3 12 1 Mounting the UPS only Assemble the two sets of feet included with the UPS and place the UPS between feet as shown in the next gures 3 12 2 Mounting the UPS plus One External Battery Assemble the two sets ...

Page 18: ...own the attached devices after safely closing open applications programs and the operating system After return of the mains voltage the UPS automatically restores power to the connected equipment and starts recharging the batteries 4 1 3 Bypass Mode If the UPS is in bypass mode the load is supplied directly from the AC mains via the internal automatic bypass The unit automatically starts up in byp...

Page 19: ... up the unit manually NOTE assuming that this functionality is activated if there is a mains failure just after the unit has automatically started up autonomy time will be short as the batteries have not been fully charged d Site Wiring Fault detection the unit can detect if input line and input neutral have been inverted and report a fault in that case e Battery test the UPS can perform a battery...

Page 20: ...ovide the operator with the current status of the UPS and the ability to change UPS operational mode Inverter ON OFF switch and LED A simpli ed block diagram of the UPS shows the current operational mode of the UPS i e line mode battery mode bypass mode Two LED indicators show the current status ON or OFF of the controllable outlets 1 and 2 Four additional LEDs provide error status UPS load percen...

Page 21: ... show output load level on LEDs 1 2 3 and 4 by default they show battery capacity level Cold Start Enable Disable Press ve seconds to enable disable cold start functionality LED 1 Site Wiring Fault Detection LED Indicates if Site Wiring Fault has been detected LED 2 Battery Fault LED Indicates if a battery fault has been detected LED 3 UPS Fault LED Indicates if a UPS fault has been detected LED 4...

Page 22: ...s 1 2 4 off Depending on fault Other UPS fault LED 13 ashing three times Three beeps Line Mode to Battery Mode LED 4 ON LED 3 ON LED 2 ON LED 1 ON LED 1 OFF LED 2 OFF LED 3 OFF LED 4 OFF LED 4 ON Continuous beep Remote Power Off warning LED 4 ashing LEDs 1 2 3 off One beep per second Overload warning LED 2 ashing LEDs 1 3 4 off One beep per second Battery disconnected or battery test fault LED 3 a...

Page 23: ...e ECO Mode LED orange illuminates if the unit is in bypass forced due to ECO mode 4 Fault LED red illuminates if the unit is reporting a fault battery fault inverter fault BUS fault 5 Inverter ON LED green illuminates if the inverter is ON 6 ESC Button goes up one level on the menu hierarchy Note press this button for three seconds to reset the LCM alarm alarm which indicates end of estimated batt...

Page 24: ...22 UK Chloride Active 945044 066 4 2 2 1 Menus and Functionalities Functions available in the menus and sub menus are explained below ...

Page 25: ...maining battery capacity level 75 50 25 or 0 below which outlet 2 2nd group of output controllable sockets automatically switches off 6 8 Cold Start Enables disables this functionality start up without mains power 6 9 Auto Re Start Enables disables this functionality automatic start up after autonomy time has nished and upon mains power comeback 6 10 ECO Mode Enables or disables this operation mod...

Page 26: ...OVERLOAD Overload detected when the unit is on bypass mode FAN FAULT Fan failure has been detected CHARGER OVERVOLTAGE Charger is delivering overvoltage internal failure DC BUS OVERVOLTAGE DC voltage on the DC bus too high internal failure DC BUS UNDERVOLTAGE DC voltage on the DC bus too low internal failure DC BUS UNBALANCE DC voltage on the DC bus unbalanced internal failure INVERTER OVERVOLTAGE...

Page 27: ...able outlets 2 groups 6 USB port 7 RS232 port 8 Fan 9 External battery pack connector 10 RJ11 port for battery pack detection cable 11 ROO RPO terminals 12 Earth screw Active 1000 T and Active 1500 T 1 Battery pack connector 2 RJ11 port for battery pack detection cable 3 Circuit breaker 4 Battery pack connector BP A1000 1500 T ...

Page 28: ...l battery pack connector 4 RJ11 port for battery pack detection cable 5 RS232 port 6 Input circuit breaker 7 Input power socket 8 Not controllable output sockets 9 Fixing point for sliding rail 10 Controllable outlets 2 groups 11 ROO RPO terminals 12 USB port 13 Earth screw Active 3000 RT 1 SNMP slot 2 Fan 3 Fan 4 External battery pack connector 5 RJ11 port for battery pack detection cable 6 RS232...

Page 29: ...fore be disconnected before carrying out maintenance work inside the UPS NOTE Under EMC regulations output cables can not be longer than 10 meters communication cables can not be longer than 3 meters and battery extension cables can not be longer than 3 meters 4 4 2 Connections 4 4 2 1 External battery packs connections WARNING Before connecting a battery pack to the UPS the circuit breaker of the...

Page 30: ... to have a pre scheduled shutdown during battery operation in order to conserve battery power for the highest priority loads 3 After all connections are made follow the instructions in the next section Start up Procedure to start your UPS and external battery packs 4 4 3 Start up Procedure ATTENTION This UPS is supplied with standard power cords and receptacles suitable for its use in your area of...

Page 31: ...ll indicate the output power If AC power is not present and cold start function is enabled the UPS will turn on the Inverter ON LED but not the Mains LED indicating that the unit is now providing output power from the battery The LCD Display will show the message MAINS FAILURE and will indicate the estimated remaining back up time ATTENTION If the display shows a message indicating OVERLOAD there ...

Page 32: ...ominal power can be used when operating in this mode For other details regarding Frequency Converter Mode please see section 4 1 5 4 4 7 UPS Shutdown Procedure Press the inverter ON OFF button The inverter will be switched off but the UPS will supply power to the connected loads via the internal bypass To turn off all outputs and shutdown it is necessary to disconnect the UPS from AC mains power T...

Page 33: ...erface cables and cards are either bundled with the unit or available as accessories 5 1 Serial Interface Two serial interfaces are available DB9 port RS232 and USB port NOTE both ports cannot be used at the same time 5 2 DB9 port The 9 pole SUB D connector pin contacts contains RS232 compatible signals NOTE this interface is electrically isolated from all other circuits Apart from the RS232 inter...

Page 34: ...LARM at pin 8 this output is low when one of the alarms BATTERY LOW AC FAIL or BYPASS ACTIVE is active 5 3 USB port As with the RS232 interface the USB port facilitates the protocol data transfer The USB port included with this UPS is classi ed as HID Human Interface Device 5 4 Interface Slot The interface slot can be tted with optional various cards The connectors designation and codes placed in ...

Page 35: ...ncy of testing can be changed via LCD Display or user software Select battery self test to be performed monthly weekly daily or none 6 4 Battery replacement ATTENTION the load attached to the UPS will not be protected against loss of input power during this procedure 6 4 1 Replacing the UPS internal batteries For replacement of batteries locates in a service access area Servicing of batteries shou...

Page 36: ...cycled by an authorized recycling center The manufacturer s service center is fully equipped to deal with such batteries in accordance with the law and with the greatest respect for the environment Contact your customer service representative to arrange for maintenance and or battery replacement The typical battery life cycle is 3 to 5 years at an ambient temperature of 25ºC However battery life i...

Page 37: ...ized recycling center The manufacturer s service center is fully equipped to deal with such batteries in accordance with the law and with the greatest respect for the environment Contact your customer service representative to arrange for maintenance and or battery replacement 6 5 Front Panel with LCD Display Installation WARNING Installation must be carried out only by quali ed technicians Depend...

Page 38: ...36 UK Chloride Active 945044 066 Tower models Rack Tower models ...

Page 39: ...ry Fault LED blinks buzzer beeps at intervals or LCD Display shows battery fault message A battery fault was detected during the automatic battery test Check that battery connector is properly seated Replace the battery module Battery Fault LED blinks buzzer sound long beep about once every hour The battery is at end of life runtime on battery is compromised Reset alarm by pressing buttons 5 and 6...

Page 40: ...ency Converter Mode is activated Input power factor 0 99 batteries charged OUTPUT Waveform Pure sinusoidal Nominal output voltage VAC 200 208 220 230 default 240 V con gurable via user software and optional LCD Display 250 V under request Voltage regulation 3 Output frequency Hz 50 60Hz 0 5 same as input or selectable in Frequency Converter Mode Harmonic distortion linear non linear load THDv Max ...

Page 41: ...0 ºC without batteries 15ºC 40ºC with batteries Altitude 0 3000m Relative humidity 10 to 90 CONNECTIONS Input 1 x IEC320 C14 10A 1 x IEC320 C20 16A Output 6 x IEC320 C13 10A 3 of them controllable 2 groups 6 x IEC320 C13 10A 3 of them controllable 2 groups 1 x IEC320 C19 16A NORMATIVES CE Mark Yes Safety EN 62040 1 EN 60950 RD TÜV CB report UL cUL EMC IEC62040 2 class C2 IEC61000 4 3 3 4 5 6 8 11 ...

Page 42: ...stive load NOTE The maximum quantity of external battery packs that can be connected to the UPS is four Active 700 T Load UPS UPS 1 BP UPS 2 BP UPS 3 BP UPS 4 BP 80W 63 min 239 min 438 min 661 min 861 min 160W 37 min 158 min 254 min 397 min 476 min 240W 26 min 91 min 197 min 262 min 372 min 320W 20 min 69 min 145 min 212 min 263 min 400W 15 min 55 min 97 min 174 min 220 min 480W 13 min 45 min 80 m...

Page 43: ... 445 min 480W 26 min 97 min 195 min 237 min 327 min 640W 19 min 73 min 153 min 207 min 237 min 800W 15 min 58 min 108 min 177 min 213 min 960W 13 min 48 min 86 min 146 min 190 min 1120W 11 min 40 min 73 min 114 min 166 min 1280W 9 min 35 min 63 min 93 min 142 min 1440W 7 min 30 min 55 min 81 min 116 min 1600W 6 min 27 min 49 min 71 min 96 min Active 2000 RT Load UPS UPS 1 BP UPS 2 BP UPS 3 BP UPS ...

Page 44: ...en 3 11 Rack Montage für USV bzw Batterieschrank nur RT Modelle 3 12 Boden Montage für USV bzw Batterieschrank für externe Batterien Nur RT Modelle 3 12 1 Montage der USV alleine 3 12 2 Montage der USV plus externer Batterie 4 Betrieb und Inbetriebnahme 4 1 Theoretischer Hintergrund 4 1 1 Netzbetrieb 4 1 2 Batteriebetrieb 4 1 3 Bypass Betrieb 4 1 4 ECO Modus 4 1 5 Frequenzkonverter Modus 4 1 6 And...

Page 45: ...7 USV abschalten 4 4 8 Remote Power Off RPO Remote On Off ROO 5 5 Kommunikationschnittstellen 5 1 Serielle Schnittstelle 5 2 DB9 Port 5 3 USB Port 5 4 Schnittstellensteckplatz 6 Wartung 6 1 Reinigung 6 2 USV Lagerung 6 3 Batterietest 6 4 Batterietausch 6 4 1 Die internen Batterien der USV austauschen 6 4 2 Entsorgen der Batterie 6 5 Installation Frontblende mit LCD Anzeige 7 Fehlerbehebung 8 Techn...