TECHNICAL DATA
67
FC
01- CA
| Flow Meter
9 .5 .1 .2 Monitoring heads CST and CSF-…
Flow measurement ranges:
The flow measurement range is determined by the inner pipe diameter (see table). It can be
calculated with the following equation:
Q = V
N
x a
Q [Nm
3
/h] - flow quantity
V
N
[m/h] - average standard velocity
a [m
2
] - inner pipe cross-section
Setting range for internal pipe diameter:
10.0 mm … 999.9 mm
Velocity range:
0 … 68 Nm/s (100 Nm/s)
Accuracy
1)
:
± 5 % MW ** / ±0.5 % MBE *
Repeatability:
± 1 % MW / ±0.5 % MBE
(5% MBE to 100 % MBE)
Temperature drift:
± 0.05 %/K/MBE
Inner pipe diameter
D in mm
Measuring range
in Nm
3
/h
Display range
in Nm
3
/h
20
76
113
30
173
254
40
307
452
50
480
706
60
692
1017
70
942
1385
80
1230
1809
90
1557
2290
100
1922
2827
150
4325
6361
200
7690
11309
250
12016
17671
300
17303
25446
400
30762
45238
500
48066
70685
600
69215
101787
700
94210
138544
800
123049
180955
900
155734
229021
1000
192265
282743