TECHNICAL DATA
69
FC
01- CA
| Flow Meter
9 .7 Sensor interface
9 .7 .1 Electrical data of the terminal for calorimetric monitoring heads
Terminal
Mnemonics
Data
XSK1
R(HEIZ)-LO
Function: terminal for negative pole of heater element
Drain output of heating current control
Max. sink current: I
sink
= 88 mA
Dielectric strength: -0.5 V … +20 V DC
XSK2
R(HEIZ)-HI
Function: terminal for positive pole of heater element
Hi-potential of heater source
Output voltage range (load dependent)
U
a
= 21 V … 24 V DC
Max. current output: I
max
= 100 mA
Not short-circuit proof
XSK3
R(Tref)-HI
Function: terminal for positive RTD * pole for medium
temperature measurement
Input resistance: > 1 G
Ω
Dielectric strength: -17 V … +30 V DC
XSK4
R(Tref)-LO
Function: terminal for negative RTD * pole for medium
temperature measurement
Input resistance: > 1 G
Ω
Dielectric strength: -17 V … +30 V DC
XSK5
AGND
Function: analogue ground
Reference potential of exitation current source for
RTD * operation
XSK6
IS
Function: output of exitation current source for
RTD * operation
Exitation current: 1 mA ± 1 %
Admissible load range: R
load
= 0 … 2 k
Ω
Dielectric strength: ±15 V DC
XSK7
SGND
Function: shield ground
XSK8
Terminals for sensor cable shielding
XSK9
R(Tdiff)-LO
Function: terminal for negative pole of the heated RTD *
Input resistance: > 1 G
Ω
Dielectric strength: -17 V … +30 V DC
XSK10
R(Tdiff)-HI
Function: terminal for positive pole of the heated RTD *
Input resistance: > 1 G
Ω
Dielectric strength: -17 V … +30 V DC
* RTD =
R
esistive
T
emperature
D
evice