manual – force
IQ
30
www.flexiforce.com
30
4.6: forceOSE
Connect:
Connect the 3pole connector of the forceOSE Optosensor kit to KL3 in the control unit.
If you use a slack rope switch, you can connect the 2pole connector to KL7.
If you use a pass door switch, you can connect the 2pole connector to KL2 1‐2 or KL2 3‐4.
Make sure a 8.2 kΩ is connected if you use KL2 (See also basic wiring diagram)
Settings optosensor
•
Use the or buttons to navigate to the "Safety device" menu.
•
Press
to enter the menu.
•
Use the or buttons to select "OSE1 KL3". Press
to confirm.
•
Use the or buttons to select "OSE". Press
to confirm.
•
Use the or buttons to select "down full rev.". Press
to confirm
•
Press to return to the main menu.
•
Press once more to enter the manoeuvring mode.
Settings for the pass door switch:
•
Use the or buttons to navigate to the "Safety device" menu.
•
Press
to enter the menu.
•
Use the or buttons to select "Safety 1" for KL2 1‐2 and "Safety 2" for KL2 3‐4. Press
to confirm.
•
Use the or buttons to select "passdoor".
•
Press
to confirm and save.
•
Press to return to the main menu.
•
Press once more to enter the maneuvering mode.
4.7 forcePSE
Connect:
Connect the 4Pole connector of the Force PSE to KL2.(green and white on 1‐2)
Make sure a 8.2 kΩ is connected if you use KL2 (See also basic wiring diagram)
If you use a slack rope switch, you can connect the 2pole connector to KL8.
If you use a pass door switch, you can connect the 2pole connector to KL2 3‐4
You don't have to adjust the slack rope switch, this is recognized by the control unit
.
Summary of Contents for ForceIQ Force100XC
Page 1: ...forceIQ manual manual version 3 0 software version 1 147 c 1 DEF5000 EN ...
Page 34: ......
Page 35: ...manual forceIQ 35 www flexiforce com 34 Appendix 6 1 Additional function terminals ...
Page 36: ...manual forceIQ 36 www flexiforce com 35 Terminal group A Terminal group B ...
Page 37: ...manual forceIQ 37 www flexiforce com Terminal group C Terminal group D ...