62
Service setting manual
EN
Para-
meter
Parameter name
Parameter description
Setting range
Default
setting
S7.2
HEAT PUMP
– MAXIMUM
TEMPERATURE
OF THE
SUPPLY
Configures the maximum heat
pump operating temperature for
weather-compensated operation.
40 ÷ 70 °C
50
S7.3
HEAT PUMP –
OPERATION
HYSTERESIS
Configures the heat pump operation
hysteresis.
2 ÷ 10 °C
3
S7.4
HEAT PUMP –
MIN.
OUTDOOR
TEMP. FOR
OPERATION
SWITCH-OFF
Configures the limit outdoor
temperature at which the heat
pump operation unconditionally
stops.
-30 ÷ 10 °C
11 - NO
STOPPING
-10
S7.5
HEAT PUMP
– OUTDOOR
TEMP. FOR
BIVALENT
OPERATION
MODE
Configures the outdoor temperature
for the bivalent operation mode
of the heat pump and the second
energy source. If the temperature is
lower than the configured one, the
controller switches to the second
energy source immediately after the
heat pump can no longer provide the
demanded water temperature. If the
temperature is higher than the con-
figured one, the controller switches
to the second energy source based
on the temperature deficit or with a
delay. This switchover mode enables
maximum use of energy from the
heat pump or use of energy from the
heat pump even if the latter can-
not provide the necessary energy.
entirely.
-30 ÷ 20 °C
-3
S7.6
HEAT PUMP
– MIN. OUT-
DOOR TEMP.
FOR MONOVA-
LENT OPERA-
TION MODE
Configures the minimum outdoor
temperature in the heat pump and
second energy source system. If the
temperature exceeds the minimum
outdoor temperature, heating is per-
formed with a heat pump exclusively.
-30 ÷ 20 °C
7
SERVICE PARAMETERS
Summary of Contents for MeiTronic W10
Page 1: ...DE DE W10B W10 W20 Weather compensated heating controller Witterungsgef hrte Heizungsregler...
Page 2: ......
Page 98: ...98 Statements EN...
Page 230: ...230...
Page 231: ......