48
Service setting manual
EN
Para-
meter
Parameter name
Parameter description
Setting range
Default
setting
S1.15
SENSOR T3
CALIBRATION
Correction of displayed measured
temperature for sensor T3.
-5 ÷ 5 K
0
S1.16
SENSOR T4
CALIBRATION
Correction of displayed measured
temperature for sensor T4.
-5 ÷ 5 K
0
S1.17
SENSOR T5
CALIBRATION
Correction of displayed measured
temperature for sensor T5.
-5 ÷ 5 K
0
S1.18
SENSOR T6
CALIBRATION
Correction of displayed measured
temperature for sensor T6.
-5 ÷ 5 K
0
S1.19
SENSOR T7
CALIBRATION
Correction of displayed measured
temperature for sensor T7.
-5 ÷ 5 K
0
S1.20
SENSOR T8
CALIBRATION
Correction of displayed measured
temperature for sensor T8.
-5 ÷ 5 K
0
Para-
meter
Parameter name
Parameter description
Setting range
Default
setting
S2.1
INFLUENCE OF
ROOM TEMP.
DEVIATION
Set the influence of room tempera-
ture deviation. Lower value means
lower influence, higher value means
higher influence.
0,0 ÷ 3,0
1
S2.2
INFLUENCE
OF ROOM
SENSOR T1
OR T8
Setting of room sensor T1 or T8 influ-
ence on the operation of first circuit.
1- automatic room sensor influence
- room sensor has no influence if
room unit is connected
- room sensor has influence if
room unit isn't connected
2- room sensor has influence
3- room sensor has no influence
This setting has affect only if S1.4=1
(for sensor T1) or S1.5=4 (for sensor
T8).
1- AUTO
2- YES
3- NO
1
S2.3
INFLUENCE
OF ROOM
UNIT RCD
Setting of room unit room RCD
influence on the operation of the
first circuit.
0- room units has no influence.
1- room unit 1 has influence.
2- room unit 2 has influence.
3- room unit 1 and 2 have influence.
0- NO
1- R.U. 1
2- R.U. 2
3- R.U. 1 & 2
1
SERVICE SETTINGS FOR THE FIRST HEATING
CIRCUIT
SERVICE PARAMETERS