50
Service setting manual
EN
Para-
meter
Parameter name
Parameter description
Setting range
Default
setting
S2.11
MAX. FLOOR
TEMPERATURE
Setting of maximum floor tempera-
ture limitation by floor heating.
Setting is active only if floor sensor
is installed and parameter S1.4=2 (for
sensor T1) or S1.5=5 (for sensor T8).
10 ÷ 50 °C
25
S2.12
MINIMUM
STAND-PIPE
TEMPERATURE
IN COOLING
MODE
Setting of minimum stand-pipe
temperature in cooling mode.
CAUTION!
Too low stand-pipe
temperature can cause dewing of
heating bodies and pipelines.
10 ÷ 20 °C
15
S2.13
SHIFT OF TEM-
PERATURE,
REQUIRED
TO ACTIVATE
STAND-PIPE
CONTROL
Shift of calculated min. stand-pipe
temperature by which the mixing
valve control will activate.
Negative values mean activation of
mixing valve control by lower
calculated stan-pipe temperatures,
positive values mean activation of
mixing valve control by higher
calculated stand-pipe temperatures.
-10 ÷ 10 °C
0
S2.14
LIMITATION OF
TEMP. DIFFER-
ENCE BE-
TWEEN STAND
AND RETURN
PIPE
Setting of maximal difference
between stand-pipe and return-pipe
temperature. This way the highest
power of heating system is limited.
Limitation of difference between
stand and return pipe is activated
with parameter S1.4=3 (for sensor T1)
or S1.5=6 (for sensor T8).
3 ÷ 30 °C
10
S2.15
CONSTANT
STAND-PIPE
TEMPERATURE
Selection of operation with constant
stand-pipe temperature.
Setting range is 10 ÷ 140 °C.
CAUTION:
This function deactivates
weather compensated control of
mixing valve.
0- NO
1- YES
0
S2.16
CIRCULATION
PUMP
SWITCH-OFF
DELAY
Setting of circulation pump
switch-off delay when there
is no requirement for heating.
0 ÷ 10 min
5
SERVICE PARAMETERS