58
Service setting manual
EN
Para-
meter
Parameter name
Parameter description
Setting range
Default
setting
S5.16
INVERTED
OUTPUT FOR
SWITCHOVER
BETWEEN
HEAT
SOURCES
By schemes with two heat sources
it can be set if output for
switchover between two heat
sources is inverted.
0- NORMAL
1- INVERTED
0
S5.17
FLUE GASES
TEMP. FOR
SWITCHOVER
TO SOLID
FUEL BOILER
In schemes with double fireplace
boiler (scheme #417 and # 418) the
flue gases sensor can be used to
measure solid fuel flue gases
temperature (parameter S1.4=9). In
such cases the switchover from oil
boiler to solid fuel boiler is activat-
ed also if flue gases temperature
exceeds set-point temperature. Set
also parameter S1.4=9 (for sensor T1)
or S1.5=10 (for sensor T8).
70 ÷ 350 °C
130
S5.18
MAX. FLUE
GASES
TEMPERATURE
Setting of max. flue gases
temperature. If flue gases
temperature exceeds setted
value, controller indicates it.
Set also parameter S1.4=9 (for
sensor T1) or S1.5=10 (for sensor T8).
70 ÷ 350 °C
200
S5.19
MIN. FLUE
GASES TEMP.
OF SOLID
FUEL BOILER
Setting of max. flue gasses
temperature of solid fuel boiler,
above which the operation of liquid
fuel boiler is disabled. This option is
used if the liquid and solid fuel boiler
are connected on the same chimney
pipe and is prohibited to have dual
boiler operation.
Also set parameter S1.4=12 (for
sensor T1) or S1.5=13 (for sensor T8).
50 ÷ 150 °C
100
SERVICE PARAMETERS