57
Service setting manual
EN
Para-
meter
Parameter name
Parameter description
Setting range
Default
setting
S5.8
DELAY OF
REPEATED
BOILER
SWITCH-ON
With this setting, we determine the
delay time after which the boiler
can be switched on again. The delay
starts when the boiler is switched off
and until the delay expires,
repeated switch-on of the
boiler will be disabled.
0 ÷ 30 min
0
S5.12
SOLID FUEL
BOILER
PROTECTION
TEMP.
Setting of solid fuel boiler protection
temperature. If this temperature is
exceeded, controller gradually starts
to increase calculated stand-pipe
temperature in circuit 1 and 2.
70 ÷ 90 °C
77
S5.13
MAX. SOLID
FUEL BOILER
OR HEAT
ACCUMULA-
TOR TEMP.
Setting of max. solid fuel boiler
temperature or heat accumulator
temperature. If this temperature is
exceeded controller transfers surplus
heat to d. h. w. storage tank and
heating circuits. Limitation of max.
stand-pipe temperature in heating
circuits remains active.
60 ÷ 160 °C
90
S5.14
MIN. BOILER
RETURN–PIPE
TEMP.
Setting of min. allowed boiler
return-pipe temperature for classic
or high-temperture boilers.
This setting is valid only by schemes
with boiler return pipe limitation.
Also set parameter S1.4=11 (for
sensor T1) or S1.5=12 (for sensor T8).
10 ÷ 90 °C
50
S5.15
SWITCHOVER
DELAY TO
CONTROLLED
HEAT SOURCE
By systems with two heat sources,
controller switches to heating with
oil boiler when the deficit of heat
occurs. Switchover is carried out with
delay. Smaller value means higher
heating comfort due to shorter delay
by switchover, higher value means
higher energy saving due to longer
delay by switchover.
0,1 ÷ 3,0
1
SERVICE PARAMETERS