FISCHER Mess- und Regeltechnik GmbH
Parameterization | 5
BA_EN_EA16
49 / 88
Pos. Value range
Description
1
Unit
Unit of the connected linear differential
pressure transmitter
2
Measuring range start
The start of the measuring range is defined
with this parameter.
3
Measuring range end
The end of the measuring range is defined
with this parameter.
4
Zero-point window
0.00 … 25.00 %
This parameter is used to set a range
around zero at which the measured value
is set to zero.
*)
*)
See section a) Characteristic curve: linear [Level 5].
NOTICE! The measuring range start must always be set to zero in the flow
measurement. Other values will lead to an error message.
Submenu: Flow rate measuring range [Level 6]
Menu path: Main menu/ Configuration/ Inputs/Analogue input 1/Characteristic
curve: Flow/Flow measuring range/
Flow rate
measuring range
5. level
6. level (Parameter)
1
unit
/h
input
2
dP primary element
100,000 Pa
input
3
volume flow
100,000
input
3
m
m
3
/h
Fig. 71:
Submenu: Flow rate measuring range
Pos. Value range
Description
1
Unit
m
3
/h
Flow measurement unit
2
Differential pressure
sensor
0 … 999999 Pa
System parameter:
Differential pressure of the differential pres-
sure sensor at the value defined by the
parameter
<Volume flow>
.
3
Volume flow
0 … 999999 m
3
/h
System parameter:
Flow rate at the value defined by the para-
meter
<dP Differential pressure>
.
The square rooted function (measuring range start and end) is automatically
calculated from the system parameters.
NOTICE! The value zero is not allowed for the parameter dP Differential
pressure sensor and leads to an error message.