FISCHER Mess- und Regeltechnik GmbH
Technical data | 6
BA_EN_EA16
83 / 88
6 Technical data
6.1 Generalities
The stated technical data only refer to the measuring value display unit EA16
and never take into account the properties of the connected measuring trans-
ducer.
The EA16 is designed as a component for panel installation and is only supplied
fully assembled and wired. Please see the supplied electro-technology docu-
ments of the respective panel for information about the electrical connection.
6.2 Input variables
6.2.1 Analogue inputs A1 ... A4
Depending on the model, the measured value display unit EA16 has 2 or 4 ana-
logue inputs for measuring transducers with output signals current of voltage
acc. to IEC 60381.
Input
range
Min. signal
range
Resolution Input
resistance
Overload protection
0 … 20 mA
4 mA
12 Bit
≤ 30 Ω
PTC
max. 32 DC/ 140 mA
4 … 20 mA
4 mA
≤ 30 Ω
PTC
max. 32 DC/ 140 mA
0 … 10 V
2.5V
≥ 200 kΩ
max. 32 V
6.2.2 Digital inputs I/O1 ... I/O4
The number of inputs depends on the number of Flex I/O channels configured
as an output. It is configured ex-works and must be stated on the order.
Quantity
Max. 4
Input voltage
5 … 32 V DC
Switching threshold
ON: 3.9V
OFF: 2.6 V
Tolerance ±10%
6.3 Output parameters
6.3.1 Analogue outputs A1 ... A4
Depending on the model, the measured value display unit EA16 has 2 or 4 ana-
logue inputs with programmable uniform signals acc. to IEC 60381.
Output
signal
Min. signal
range
Resolution Signal range
0 … 20 mA
4 mA
12 Bit
0.0 … 21.5 mA
4 … 20 mA
4 mA
0.0 … 21.5 mA
0 … 10 V
2.5V
0.0 … 10.5 V