5 | Parameterization
FISCHER Mess- und Regeltechnik GmbH
34 / 88
BA_EN_EA16
Menu: Switch output 1 [Level 4]
The switch outputs can be assigned to both the input signals and also the col-
our changes. Depending on the selected assignment, the following submenu
also changes.
A. Assignment to the input signals
Menu path: Main menu/Configuration/Switch outputs/Switch output 1
Switch output 1
Assignment Input 1
Contact type: NO
Function: Hysteresis
Activation point
3. Level
4. Level (Parameter)
input
1
2
3
4
5
15,000 Pa
Deactivation point
15,000 Pa
6
Switch delay
0.000 s
input
input
Menu Switch output 1 (Assignment: Input signals)
Pos. Value range
Description
1
Assignment Input: 1
Assignment Input: 2
Assignment Input: 3
Assignment Input: 4
Assignment: Colour change
Assignment Input: -
This parameter assigns switch output 1 to
an input (1...4) or switches it off (-).
2
Contact type: Make con-
tact
Contact type: Open con-
tact
This parameter defines whether or not the
switch output 1 works with an open contact
or make contact.
The parameter list changes depending on the parameter
function
:
Hysteresis
3
Function: Hysteresis
Hysteresis function
4
Switch-on point
An input window opens. The possible input
limit values depend on the set measuring
range.
5
Switch-off point
Window
3
Function: Window
Window function
4
Window max.
An input window opens. The possible input
limit values depend on the set measuring
range.
5
Window min.
6
Switch delay
0 = OFF
0.01 … 10800 s
A switch delay of the switch output can be
defined in 10 ms steps with this parameter.