5 | Parameterization
FISCHER Mess- und Regeltechnik GmbH
48 / 88
BA_EN_EA16
c) Function: Flow rate [Level 5]
Menu path: Main menu/Configuration/Inputs/Analogue input 1/Characteristic
curve/
characteristic curve
Level 4
Level 5 (parameters)
Function: flow
1
5
Damping
1.000 s
Input
Lin. Input range
2
Flow measur. range
3
Limit:
4
w
Sub menu
Sub menu
Fig. 69:
Menu characteristic curve flow rate
The parameter value
<Function: Flow>
is used to switch the input characeristic
curve to a square rooted characteristic curve that is adapted to the flow meas-
urement. There are two additional submenues on the parameter level.
• In the
the input range is configured according to the the technical data of the
sensor used.
• In the
submenu: Flow measuring range [
the measuring range is automatically configured using system parameters.
Pos. Value range
Description
1
Function: Flow rate
The characteristic curve type ‚
flow
‘ is se-
lected.
2
Lin. input range
Submenu for configuration of the linear in-
put range.
3
Flow rate measuring
range
Submenu for configuring the measuring
range.
4
Limits
Yes (standard value)
No
The display and output signal can be lim-
ited to the set measuring range (start - end)
with this parameter.
5
Damping
0.000 … 30.000 s
The input signal can be dampened with this
parameter.
Submenu: Lin. input range [Level 6]
Menu path: Main menu/ Configuration/ Inputs/Analogue input 1/Characteristic
curve: flow/lin. measuring range/
Lin input range
Level 5
Level 6 (parameters)
1
Unit
Pa
Input
2
Measur. range start
0,000 Pa
Input
3
Measur. range end
50,000 Pa
Input
4
Zero-point window
1,000 %
Input
Fig. 70:
Submenu: Lin. input range