Installation Instructions
14.7.16
Kapitel/Chapter 7: Installation Instructions - Seite/Page 67
Install an appropriate fuse and a battery circuit breaker in the plus pole cable of the battery, but with a distance to the
battery of up to 300 mm (12 inch) at maximum.
The cable from the battery to the safety device must be secured with protective pipe/sleeve against chafing through.
For the connection use self-extinguishing and fire-protected cables, which are appropriate for temperatures up to
90 °C, 195 °F.
The batteries must be installed in such a way that they do not chafe through or other mechanical load can be
stripped.
The battery poles must be secured against unintentional short-circuit.
The positive battery cable within the generator must be shifted in such a way that it is protected against heat and
vibrations by appropriate sleeve/protective pipe. It must be shifted in such a way that it does not affect rotary parts or
parts, that become hot in operation, e.g. wheel, exhaust elbow union, tail pipe and the engine. Do not lay the cable
too tautly, since otherwise it could be damaged.
Make a test run after the installation and check the laying of the batteries during the test run and afterwards. If
necessary, correct the laying.
Examine regularly the cable laying and the electrical connections.
Fig. 7.12.1-1: Positive Battery Cable
Positive battery cable
The positive (+) battery cable is connected directly to the
solenoid switch of the starter.
Fig. 7.12.1-2: Negative Battery Cable
Negative battery cable
The negative (-) battery cable is connected to the engine
foot.
Note! The battery negative pole may not be connected
with the boat ground or with the protective grounding of
the 120 V installation!