Installation Instructions
Seite/Page 64 - Kaptitel/Chapter 7: Installation Instructions
14.7.16
Fig. 7.10.0-2: Fuel system - schema
Fig. 7.10-3: externer Feinfilter
External fine filter
At generators with Kubota EA 300 or Farymann engines, the
fine filter is delivered with the generator. This fine filter should
be installed in the fuel feed line next to the generator.
representative picture
7.10.1 Connection of the fuel lines at the tank
Note:
General fuel feed and return line must be connected to the
tank at separate connection points.
Connection of the return pipe to the tank
The return pipe connected to the tank must be dropped to the same depth as the suction pipe, if the generator is
mounted higher than the tank, in order to prevent fuel running back into the tank after the motor has been switched
off, which can lead to enormous problems, if the generator is switched off for a long period.
Non-return valve in the suction pipe
A non-return valve must be fitted to the suction pipe, which prevents the fuel flowing back after the generator has
5
2
3
4
1
6
1. Fuel tank
2. external fuel pump
3. external fuel prefilter with water separator
4. Non return valve
5. Fuel fine filter
6. Generator