General operation
Seite/Page 146 - Kaptitel/Chapter 13: General operation
14.7.16
Fig. 13.4.7-1: Resetting the time until the next service
Resetting the time until the next service
By actuating the Start/Stop button again, you can reset the
service interval to the original interval. The service interval for
each generator type is stored in the software.
The controller is switched off after resetting the service
interval. After restart, the new value will be displayed in the
service screen.
13.4.8 Priming the fuel system ("Prime Fuel")
To prime the fuel system, the Panda iControl2 offers the option of separately activating the fuel pump. In the set-up
menu, select the menu item "Prime fuel" and confirm your selection using the Start/Stop button.
Fig. 13.4.8-1: Set-up menu
Actuating the Start/Stop button again will switch on the
fuel pump for a duration of max. 30 seconds. After that,
the fuel pump will shut off automatically.
Naturally, you can also switch off the fuel pump manually.
For this purpose, confirm the menu item "Prime fuel" again,
and switch off the fuel pump using the Start/Stop button.
13.4.9 Selecting and saving a unit for the temperature value output
With the Panda iControl2 panel, you can output the temperature values on the display in degrees Celsius [°C] or in
degrees Fahrenheit [°F]. The unit can be switched with the control panel. In the set-up menu, select the menu item
"Degree C/F" and confirm your selection using the Start/Stop button.
Using the cursor buttons, select 0' for outputting all temperatures in degrees Celsius [°C] or 1' for outputting them in
degrees Fahrenheit [°F]. To confirm your selection, actuate the Start/Stop button.
You can enter additional settings in the set-up menu, or you can exit the set-up menu with "Save & Exit". Your
selections will then be saved to the EEPROM of the Panda iControl2 panel.
After restarting the system with the On/Off button, your settings will take effect, and all temperatures will be output
with the selected unit.
Settings options:
0 Output of all temperatures in degrees Celsius [°C]
1 Output of all temperatures in degrees Fahrenheit [°F]
13.5 iControl2-Emergency-Stop
The iControl2 is prepared for the connection of an emergency stop. The socket for the emergency stop is in the
cable harness integrated and bridged (1X1, optional emergency off). The bridge must be removed and the
emergency stop connected.
After the emergency stop is initiated, the servo drives to zero position, all out of the iControl controller are switched
off and the power supply to the inverter is switched off.