Inverter Panda PMGi
14.7.16
Kapitel/Chapter 11: Inverter Panda PMGi - Seite/Page 111
11.7.2 Settings in the Victron VE Configure II Software - Inverter
Fig. 11.7.2-1: Settings in the Victron VE configure II Software
11.7.2.1 Assist current boost factor
To reduce the action of the power inverter on the iGenerator, the Assist current boost factor must be reduced from
2.0 to1.3. Wrong settings will cause bad rpm control of the generator.