Chapter V Functional Parameter TableHigh-performance Universal Inverter User Manual
— 36 —
FC
name
description
Factory value
attribute
09-27
First
secondary
fault
module
temperature
※
09-28
First
secondary
fault
input
terminal status
※
09-29
First
secondary
fault
output
terminal status
※
10 Groups of protection parameters
10-00
Motor
overload
protection
selection
0: Do not move
1: Ordinary motor
2: Frequency conversion motor
2
●
10-01
Motor
overload
protection factor
20.0%~120.0%
100.0%
○
10-02
Overvoltage stall
protection
enables
0: Invalid 1: valid
1
○
10-03
Over-voltage stall
action voltage
The 220V model: 120~150%
120%
○
The 380V model: 120~150%
140%
10-04
Overflow
protection
options
Individual bit: Overcurrent protection enables
0 Invalid, 1 valid
Ten digits: the hardware current-limiting
protection is enabled
0 is Valid, and 1 is invalid
100 bits: inverter unit overcurrent fault
unblocking selection
0: Can be lifted
1: The blockade can be lifted after 60 seconds
2: Keep blocking, and the re-power is lifted
101
●
10-05
Over-drain speed
protection current
50.0~200.0%
Model
determination
●
10-06
Excessive loss rate
decline rate
0.00~50.00Hz (value per second)
10.00Hz
●
10-07
Insufficient input
and output phase
Individual bit: Enter the default phase protection
enabled
11
○