High Performance General Inverter User Manual Chapter V Functional Parameter Table
— 23 —
FC
name
description
Factory value
attribute
05-11
Stop the DC brake
current
0.0~100.0%
0.0%
○
05-12
Stop the DC brake
time
0.00~50.00s
0.00s
○
05-16
Reverse the dead
zone time
0.0~3600.0s
0.00s
○
05-17
Reverse
the
switch mode
0: Zero frequency switch
1: Start the frequency switching
2: Stop the speed switching
0
●
05-18
Stop the speed
0.00~100.00Hz
0.50Hz
●
05-19
Stop the speed
check-out mode
0: Check out by the speed setting value
1: Check the feedback value by speed
1
●
05-20
Feedback speed
detection time
0.00~100.00s
0.05s
●
05-21
Start delay
0.0~60.0s
0.0s
○
05-22
Stop speed delay
0.0~100.0s
0.0s
○
05-23
Brake unit action
0: Disable 1: enabled
1
○
05-24
Brake unit action
voltage
200.0~2000.0V
(220V: 380V, 380V: 700V)
Model
determination
○
05-25
Excitation braking
strength
0~150
0: Disable
Greater than 0: the greater the value, the better
the braking effect
0
○
06 Group of input terminal parameters
06-00
HDI input pattern
0: High-speed pulse input
1: Terminal switch quantity input
1
●
06-01
X1
terminal
function selection
0: No function
1: Forward turn operation (FWD)
2: Reverse operation (REV)
3: Three-line operation control
4: Forward turn-inch move (FJOG)
5: Reverse motion (RJOG)
6: Free parking
7: Fault reset
1
●