High Performance General Inverter User Manual Chapter V Functional Parameter Table
— 37 —
FC
name
description
Factory value
attribute
protection
Ten digits: the output lack of phase protection
enabling
0 Invalid, 1 valid
10-08
Overload
and
overload
protection action
Individual bit: Overload overload warning
selection
0: Motor is under overload warning
1: The frequency converter lacks the overload
warning
Ten places: under-overload overload action for
choice
0: The frequency converter lacks the overload
warning and continues to operate
1: frequency converter overload warning,
shutdown after overload
2: The frequency converter has overload warning
and continue to run, and stop after underload
3: Stop ter stops after underload
Hundred: under overload protection can be
0: The whole process is effective
1: Effective at a constant speed
000
○
10-09
Overload
detection
quasi-position
(10-11)~200%
Model
determination
○
10-10
overload
detection time
0.1~3600.0s
1.0s
○
10-11
Warload detection
quasi-position
0~(10-09)
50%
○
10-12
Time to check out
the load
0.1~3600.0s
1.0s
○
10-13
Number
of
automatic
reset
times of failures
0~10
0
○
10-14
Automatic
fault
reset interval
0.1~3600.0s
1.0s
○
10-15
Overpressure
point setting
0~800V
Model
determination
○
10-16
Underpressure
point setting
0~350V
Model
determination
○