83
®
EK85
Oxygen probe cell temperature (ºC)
Temperature of oxygen cell, nominal 650ºC.
F70 will be generated if outside the window 600ºC (after 15 minutes of power on) to
700ºC
EK86
Oxygen error (%)
Error between O2 measured value and O2 setpoint
EK87
Trim deviation (% flow)
Deviation in air flow imposed by trim (-25 to +25%)
EK88
Excess air (%)
Excess combustion air at the current firing position
EK89
Oxygen setpoint (%)
Current oxygen setpoint. This is only available if trim is enabled and working.
EK90-101
Fuel 1 - Option 5 positioning error
(º for motors, 0 – 999 for inverters)
How far a drive is away from its setpoint
A positioning fault will be generated if the error is greater than 1º for 15 seconds or 5º
for 1 second.
EK102-113
Drive speed (s/90×)
The measured time taken for each motor to move over 90×.
NUMBER
NAME
DESCRIPTION