55
®
* If all drives have not been selected, then not all drive numbers will be available.
Option 08.1 - Ignition time (0 – 999)*
The time (in seconds) at which the drives remain in their ignition positions before the system moves
the drives to low fire. May be set between 0 and 999 seconds inclusive.
Option 08.2 - Low fire hold time (0 – 999)*
The time (in seconds) at which the drives remain in their low fire positions before the system begins
to modulate. May be set between 0 and 999 seconds inclusive.
Option 09.1 - Post purge time (1 – 999)*
The time (in seconds) at which the drives remain in their purge positions after the burner has turned
off. If this option is set to 0, the drives will move straight to their closed positions after the burner has
turned off and there is no post purge. If a post purge is desired, this option may be set between 1 and
999 seconds inclusive.
Note: This optional software controlled postpurge must not be used to replace the pre-purge as dic-
tated by the external burner controller.
Option 10.1 - Alarm relay level (0 – 7)*
The alarm relay may be selected to operate for different types of alarms:
0
- Alarm relay off
1
- Flue gas limit faults only
2
- Secondary (24 hour) faults only
OPTION 07.0
PROFILE NUMBER
0 - DEFAULT TO AIR DAMPER 1
1 - SELECT PER ‘FUEL’
07.1
Profile 1
1 - 12
* see table on the following page
07.2
Profile 2
07.3
Profile 3
07.4
Profile 4
07.5
Profile 5
07.6
Profile 6
07.7
Profile 7
DRIVE NO.
’*’, SEE
BELOW)
DRIVE NAME
1
Fuel 1
2
Fuel 2
3
Fuel 3
4
Option 1
5
Option 2
6
Option 3
7
Air damper 1
8
Air damper 2
9
Air damper 3
10
Air damper 4
11
Option 4
12
Option 5