37
®
Interface to Auxiliary Equipment
The interface cabling, to either flue gas analyzers or systems
connected to the 4-20mA outputs, must be overall braid
screened 2-core PVC insulated 24
AWG
– 7/32
AWG
(300V
80°C), for all signals. Wiring must comply with all
applicable codes, ordinances and regulations and where
required must comply with NEC Class 1 (Line Voltage)
wiring. Terminate the screen
at the unit only
using the
cable clamp provided.
If this cable is run in conduit with other cables its
specification may need to be increased to ensure its voltage
rating exceeds the maximum voltage carried by any other
cable in the same conduit.
SOx + INPUT PM18
SOx – INPUT PM17
NOx + INPUT PM16
NO x – INPUT PM15
PM14
SMOKE + INPUT PM13
SMOKE - INPUT PM12
CO + INPUT PM11
CO – INPUT PM10
PM9
AUX 1 + INPUT PM8
AUX 1 - INPUT PM7
AUX 2 + INPUT PM6
AUX 2 - INPUT PM5
OUTPUT 1 + PM4
OUTPUT 1 - PM3
OUTPUT 2 + PM2
OUTPUT 2 - PM1
SOx
monitor
NOx
monitor
Smoke
monitor
CO
monitor
AUX 1
INPUT
AUX 2
INPUT
AUX 1
OUTPUT
AUX 2
OUTPUT