60
Option 20.0 - Profile mapping default (0 – 1)*
Option 20.1 - 20.7 Profile mapping (1 – 7)*
If option parameter 20.0 is set to 0, the profile mappings will assume default values. In this case, the
profile 1 input selects fuel 1, profile 2 input selects fuel 2 and profile 4 input selects fuel 3.
If option parameter 20.0 is set to 1, it is possible to determine which fuels are to be fired when a
given profile is selected. Refer to the table on the following page for details.
For example, if fuels 2 and 3 are to be fired when profile 2 is selected, set option parameter 20.2 to 6.
Option 21.0 - Default air drive select (0 / 1)*
Options 21.1 to 21.7 - Air drive select (0 / 1) *
It is possible to prevent selected air drives from being used for each profile. Option 21.0 specifies
whether this is the case.
0
- All mapped air drives will be used for every profile.
1
- It is possible to stop air damper 2, air damper 3 and air damper 4 from being used for
each profile by using option parameters 21.1 to 21.7.
Option parameters 21.1 to 21.7 choose if certain air dampers will be used for profiles 1 to 7. The
parameters may be set to the following values (provided that option 21.0 = 1):
0
- All air drives will be used except air dampers 2, 3 and 4.
1
- All air drives will be used except air dampers 3 and 4.
2
- All air drives will be used except air dampers 2 and 4.
3
- All air drives will be used except air damper 4.
4
- All air drives will be used except air dampers 2 and 3.
5
- All air drives will be used except air damper 3.
6
- All air drives will be used except air damper 2.
7
- All air drives will be used.
For example, it is possible to set up the system so that air damper 2 is not used for profile 3 by setting
option parameter 21.3 to 6. See section xxx.
Option 22.1 - Inverter control accuracy (0 / 1)*
This parameter affects all inverters connected to the unit.
0
- Low accuracy (normal setting). Control will be performed to within approximately
±0.45Hz for a 0-60Hz system.
1
- High accuracy. Control will be performed to within approximately ±0.15Hz for a 0-
60Hz system.
Note: When using the high accuracy setting, the unit may have difficulty with controlling the speed
of the inverter. If this occurs, use the low accuracy setting for reliable operation.
OPTION PROFILE
NUMBER
0- DEFAULT TO CORRESPONDING FUEL
1 - SELECT PER “PROFILE”
20.1
Profile 1
1 -7, where:
1 = Fuel 1only
2 = Fuel 2 only
3 = Fuel 1 + 2
4 = Fuel 3 only
5 = Fuel 1 + 3
6 = Fuel 2 + 3
7 = Fuel 1, 2 + 3
20.2
Profile 2
20.3
Profile 3
20.4
Profile 4
20.5
Profile 5
20.6
Profile 6
20.7
Profile 7